JOHNSON CONTROLS
36
FORM 150.63-NM6 (1020)
Installation
See Notes and Legend on page 38.
OPTIONAL MULTIPLE POINT POWER SUPPLY CONNECTIONS – YCUL0125 - YCUL0275
Two Field Provided Power Supply Circuits to the condensing unit. Field connections to Factory Provided Terminal Blocks (standard), Non-
Fused Disconnect Switches (optional), or individual System Circuit Breakers (optional) per electrical system.
TABLE 10 –
OPTIONAL MULTIPLE POINT POWER SUPPLY CONNECTIONS
SINGLE POINT FIELD SUPPLIED WIRING
SYSTEM #1 COMPRESSOR & FAN
MODEL
YCUL VOLT HZ MCA
1
MIN
N/F
DISC
SW
2
D.E. FUSE CKT. BKR.
5
INCOMING (LUGS) WIRE RANGE
6
COMPR. #1 COMPR. #2 COMPR. #3
FANS
FACTORY SUPPLIED OPTIONAL
MIN
3
MAX
4
MIN MAX
RLA LRA RLA LRA RLA LRA QTY FLA
(EA)
SINGLE POINT DISCONNECT BREAKER
0125
380/415 50 87
100
100 100 100 100
# 10 - # 1
# 14 - 1/0
# 14 - 1/0 16.6 127 16.6 127
—
—
2
4.0
0145
380/415 50 94
150
100 110 100 110
# 10 - # 1
# 2 - 4/0
# 14 - 1/0 19.9 167 19.9 167
—
—
2
4.0
0161
380/415 50 101
150
110 110 110 110
# 10 - # 1
# 2 - 4/0
# 2 - 4/0
19.9 167 19.9 167
—
—
2
4.0
0171
380/415 50 110
150
125 125 125 125
# 10 - # 1
# 2 - 4/0
# 2 - 4/0
23.9 198 23.9 198
—
—
2
4.0
0185
380/415 50 118
150
125 125 125 125
# 10 - 3/0
# 2 - 4/0
# 2 - 4/0
23.9 198 23.9 198
—
—
2
4.0
0211
380/415 50 131
150
150 150 150 150
# 10 - 3/0
# 2 - 4/0
# 2 - 4/0
19.9 167 19.9 167
19.9
167
2
4.0
0235
380/415 50 141
200
150 150 150 150
# 10 - 3/0
# 6 - 350
# 2 - 4/0
19.9 167 19.9 167
19.9
167
2
4.0
0255
380/415 50 154
200
175 175 175 175
# 10 - 3/0
# 6 - 350
# 4 - 300 23.9 198 23.9 198
23.9
198
2
4.0
0275
380/415 50 166
200
175 175 175 175
# 10 - 3/0
# 6 - 350
# 4 - 300 23.9 198 23.9 198
23.9
198
2
4.0
Summary of Contents for YCUL0045
Page 13: ...JOHNSON CONTROLS 13 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 35: ...JOHNSON CONTROLS 35 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 71: ...JOHNSON CONTROLS 71 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 79: ...JOHNSON CONTROLS 79 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 117: ...JOHNSON CONTROLS 117 FORM 150 63 NM6 1020 2 This page intentionally left blank...
Page 120: ...JOHNSON CONTROLS 120 FORM 150 63 NM6 1020 Unit Controls THIS PAGE INTENTIONALLY BLANK...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM6 1020 3 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 63 NM6 1020 4 LD08801...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 63 NM6 1020 4 LD08946...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 63 NM6 1020 4 LD08800...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 63 NM6 1020 4 LD08776...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 63 NM6 1020 4 LD08804...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 63 NM6 1020 4 LD08781...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 63 NM6 1020 4 LD08803...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 63 NM6 1020 4 LD08807...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 63 NM6 1020 4 LD08785...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 63 NM6 1020 4 LD08806...