Unit Controls
SUCTION PRESSURE CONTROL
The setpoint in Suction Pressure Control is the suction
pressures each individual system on the condensing unit
will control to /- the cooling range. The Setpoint
High Limit is the Setpoint plus the Cooling Range. The
Setpoint Low Limit is the Setpoint minus the Cooling
Range. Each system is controlled independently of each
other according to its setpoint and cooling range.
Each system must have its own zone thermostat. If the
respective zone thermostat is closed, the lead compressor
on that system will be energized. In addition the liquid
line solenoid to that system will be energized. Upon
energizing any compressor the 60 second Anti-Coin-
cidence timer will be initiated.
If after 150 seconds of run-time the suction pressure is
still above the Setpoint High Limit, the next compressor
in sequence will be energized. Additional loading stages
are energized at a rate of once every 150 seconds if
the suction pressure remains above the Setpoint High
Limit. Each system will have its own load timer of 150
seconds.
If the suction pressure falls below the Setpoint High
Limit and greater than the Setpoint Low Limit, loading
and unloading do not occur. This area of control is called
the control range.
If the suction pressure falls below the Setpoint Low
Limit, unloading (compressors cycling off) occurs at
a rate of 30 seconds per system. The zone thermostat
must be satisfied before the last compressor in the sys
-
tem cycles off, even if the suction pressure is below the
Setpoint Low Limit.
Hot Gas Bypass solenoid will be energized as the last
stage of unloading. If the zone thermostat calls for cool-
ing when the suction pressure is below the Setpoint Low
Limit, the first stage compressor will be energized with
the hot gas solenoid.
It should be noted that the zone thermostat has ultimate
control. As long as the zone thermostat is calling for
cooling, at least compressor will be running, regardless
of whether the suction pressure is below Setpoint Low
Limit.
Figure 16 illustrates loading and unloading in Suction
Pressure Control Mode. Refer to section on Setpoints
Keys for programmable values.
FIG. 16
– SUCTION PRESSURE CONTROL
30 second
control range
150 second
unloading
(no compressor staging)
loading
67 PSIG (4.6 BAR) 73 PSIG (5.0 BAR)
Setpoint
70 PSIG (4.8 BAR)
Setpoint = 70 PSIG (4.8 BAR)
Control Range = 3 PSIG ( 20.7 kPa)
Setpoint
Low Limit
Setpoint
High Limit
Summary of Contents for YCUL0045
Page 13: ...JOHNSON CONTROLS 13 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 35: ...JOHNSON CONTROLS 35 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 71: ...JOHNSON CONTROLS 71 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 79: ...JOHNSON CONTROLS 79 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 117: ...JOHNSON CONTROLS 117 FORM 150 63 NM6 1020 2 This page intentionally left blank...
Page 120: ...JOHNSON CONTROLS 120 FORM 150 63 NM6 1020 Unit Controls THIS PAGE INTENTIONALLY BLANK...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM6 1020 3 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 63 NM6 1020 4 LD08801...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 63 NM6 1020 4 LD08946...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 63 NM6 1020 4 LD08800...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 63 NM6 1020 4 LD08776...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 63 NM6 1020 4 LD08804...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 63 NM6 1020 4 LD08781...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 63 NM6 1020 4 LD08803...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 63 NM6 1020 4 LD08807...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 63 NM6 1020 4 LD08785...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 63 NM6 1020 4 LD08806...