JOHNSON CONTROLS
92
FORM 150.63-NM6 (1020)
Unit Controls
PRINT KEY
The PRINT key allows the operator to obtain a printout
of real-time system operating data or a history printout
of system data at the “instant of the fault” on the last six
faults which occurred on the unit. An optional printer is
required for the printout.
OPERATING DATA PRINTOUT
Pressing the PRINT key and then OPER DATA key al-
lows the operator to obtain a printout of current system
operating parameters. When the OPER DATA key is
pressed, a snapshot will be taken of system operating
conditions and panel programming selections. This data
will be temporarily stored in memory and transmission
of this data will begin to the printer. A sample Operating
Data printout is shown below. (Note: Not all values are
printed for all models.)
See Service And Troubleshooting section
for Printer Installation information.
YORK INTERNATIONAL CORPORATION
MILLENNIUM CONDENSING UNIT
UNIT STATUS
9:32AM 26 NOV 02
SYS 1
ANTI-RECYCLE TIMER 59 SEC
SYS 2
ANTI-RECYCLE TIMER 59 SEC
OPTIONS
AMBIENT CONTROL
STANDARD
LOCAL/REMOTE MODE
REMOTE
CONTROL MODE
DISCHARGE AIR
LEAD/LAG CONTROL
AUTOMATIC
FAN CONTROL
DISCHARGE PRESS
CURRENT FEEDBACK
NONE
COMPRESSOR LEAD/LAG
DISABLED
SOFT START
DISABLED
PROGRAM VALUES
DSCH PRESS CUTOUT
395 PSIG
SUCT PRESS CUTOUT
44 PSIG
LOW AMBIENT CUTOUT
25.0 DEGF
ANTI RECYCLE TIME
300 SECS
FAN CONTROL ON PRESS
240 PSIG
FAN DIFF OFF PRESS
65 PSIG
NUMBER OF COMPRESSORS
4
REFRIGERANT TYPE
R-22
REMOTE UNIT ID PROGRAMMED
0
UNIT DATA
DISCHARGE AIR TEMP
67.0 DEGF
COOLING RANGE
55.0 +/- 5.0 DEGF
AMBIENT AIR TEMP
55.2 DEGF
LEAD SYSTEM
SYS 1
EVAPORATOR PUMP
ON
EVAPORATOR HEATER
OFF
ACTIVE REMOTE CONTROL
ISN
SOFTWARE VERSION
C.MMC.03.02
SYSTEM 1 DATA
COMPRESSOR STATUS
OFF
RUN TIME
0- 0- 0- 0 D-H-M-S
SUCTION PRESSURE
68 PSIG
DISCHARGE PRESSURE
271 PSIG
SUCTION TEMPERATURE
49.9 DEGF
LIQUID LINE SOLENOID
OFF
HOT GAS BYPASS VALVE
OFF
CONDENSER FAN STAGES
OFF
SYSTEM 2 DATA
COMPRESSOR STATUS
OFF
RUN TIME
0- 0- 0- 0 D-H-M-S
SUCTION PRESSURE
75 PSIG
DISCHARGE PRESSURE
247 PSIG
SUCTION TEMPERATURE
57.2 DEGF
LIQUID LINE SOLENOID
OFF
CONDENSER FAN STAGES
OFF
DAILY SCHEDULE
S M T* W T F S
*=HOLIDAY
SUN START=00:00AM
STOP=00:00AM
MON START=00:00AM
STOP=00:00AM
TUE START=00:00AM
STOP=00:00AM
WED START=00:00AM
STOP=00:00AM
THU START=00:00AM
STOP=00:00AM
FRI START=00:00AM
STOP=00:00AM
SAT START=00:00AM
STOP=00:00AM
HOL START=00:00AM
STOP=00:00AM
Summary of Contents for YCUL0045
Page 13: ...JOHNSON CONTROLS 13 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 35: ...JOHNSON CONTROLS 35 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 71: ...JOHNSON CONTROLS 71 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 79: ...JOHNSON CONTROLS 79 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 117: ...JOHNSON CONTROLS 117 FORM 150 63 NM6 1020 2 This page intentionally left blank...
Page 120: ...JOHNSON CONTROLS 120 FORM 150 63 NM6 1020 Unit Controls THIS PAGE INTENTIONALLY BLANK...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM6 1020 3 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 63 NM6 1020 4 LD08801...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 63 NM6 1020 4 LD08946...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 63 NM6 1020 4 LD08800...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 63 NM6 1020 4 LD08776...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 63 NM6 1020 4 LD08804...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 63 NM6 1020 4 LD08781...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 63 NM6 1020 4 LD08803...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 63 NM6 1020 4 LD08807...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 63 NM6 1020 4 LD08785...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 63 NM6 1020 4 LD08806...