![background image](http://html1.mh-extra.com/html/york/ycul0045/ycul0045_installation-operation-and-maintenance_4223634098.webp)
JOHNSON CONTROLS
98
FORM 150.63-NM6 (1020)
This message indicates that the cooling setpoint is un-
der REMOTE control. When under remote control, the
cooling setpoint will be determined by a remote device
such as an ISN control. The message also indicates that
the control point is based on Discharge Air Temperature
leaving the evaporator.
This message indicates that the cooling setpoint is under
REMOTE control. When under remote control, the cool-
ing setpoint will be determined by a remote device such
as an ISN control. This message also indicates that the
control point is based on Suction Pressure.
Immediately after the control mode message is dis-
played, the COOLING SETPOINT entry screen will
be displayed. If the unit is programmed for Discharge Air
Temperature the following message will be displayed:
(Discharge Air Temperature control)
The above message shows the current Discharge Air
temperature SETPOINT at 55.0°F (notice the cursor
positioned under the number 5). Pressing either the UP
or DOWN arrow will change the setpoint in .5°F incre
-
ments. After using the UP and DOWN arrows to adjust
to the desired setpoint, the ENTER/ADV key must be
pressed to enter this number into memory and advance
to the RANGE SETPOINT.
This will be indicated by the cursor moving under the
RANGE setpoint. The UP and DOWN arrow keys are
used to set the RANGE, in .5 °F increments, to the
desired RANGE setpoint. After adjusting the setpoint,
the ENTER/ADV key must be pressed to enter the data
into memory.
The Discharge Air temperature SETPOINT is pro-
grammed from 45°F to 70°F. The Control Range is
programmed from 3.0°F to 10°F.
Unit Controls
If the unit was programmed for Suction Pressure control,
the following message would be displayed instead of the
previous message.
(Suction Pressure control)
The setpoint and range are programmed with the UP
arrow. DOWN arrow, and ENTER/ADV key as de
-
scribed in the previous setpoint message. The setpoints
in Suction Pressure Control are the suction pressures
of each individual system on the condensing Unit and
will control to /- the cooling range. This method
of control cannot be used unless the unit is equipped
with suction transducers (optional on YCUL0045 -
YCUL0185).
On two system units (YCUL0125 - YCUL0275), each
system is controlled independently of each other ac-
cording to its own setpoint and cooling range, so there
will be two similar displays - a setpoint and range for
both system 1 and system 2.
The Suction Pressure SETPOINTS are programmable
from 60 PSIG to 90 PSIG. The Control Range is pro-
grammable from 2 PSIG to 10 PSIG.
Both Discharge Air Temperature and Suction Pressure
control are described in detail under the section on Ca-
pacity Control.
Pressing the COOLING SETPOINTS again, after setting
the “local” setpoint(s), will display the remote setpoint
and cooling range. This display automatically updates
about every 2 seconds. Notice that these setpoints are
not “locally” programmable, but are controlled by a
remote device such as an ISN control. These setpoints
would only be valid if the unit was operating in the
REMOTE mode. The following messages illustrate
both Discharge Air Temperature and Suction Pressure
control respectively.
(Discharge Air Temperature control)
(Suction Pressure control)
R E M S E T P = 5 5 . 0 ° F
R A N G E = + / - 5 . 0 ° F
R E M S P X = 7 0 P S I G
R A N G E = + / - 3 P S I G
S E T P O I N T = 5 5 . 0 ° F
R A N G E = + / - 5 . 0 ° F
S Y S X S P = 7 0 P S I G
R A N G E = + / - 3 P S I G
R E M O T E D I S C H A R G E
A I R T E M P C O N T R O L
R E M O T E S U C T I O N
P R E S S U R E C O N T R O L
Summary of Contents for YCUL0045
Page 13: ...JOHNSON CONTROLS 13 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 35: ...JOHNSON CONTROLS 35 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 71: ...JOHNSON CONTROLS 71 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 79: ...JOHNSON CONTROLS 79 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 117: ...JOHNSON CONTROLS 117 FORM 150 63 NM6 1020 2 This page intentionally left blank...
Page 120: ...JOHNSON CONTROLS 120 FORM 150 63 NM6 1020 Unit Controls THIS PAGE INTENTIONALLY BLANK...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM6 1020 3 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 63 NM6 1020 4 LD08801...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 63 NM6 1020 4 LD08946...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 63 NM6 1020 4 LD08800...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 63 NM6 1020 4 LD08776...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 63 NM6 1020 4 LD08804...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 63 NM6 1020 4 LD08781...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 63 NM6 1020 4 LD08803...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 63 NM6 1020 4 LD08807...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 63 NM6 1020 4 LD08785...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 63 NM6 1020 4 LD08806...