OPTION 3 – AMBIENT CONTROL TYPE:
(YCUL0045 - 0255 ONLY)
The low ambient cutout is adjustable from 25°F to 60°F
(-3.9°C to 15.6°C).
or
The low ambient cutout is programmable down to 0°F
(-17.8°C).
A low ambient kit MUST be installed for
this option to be chosen. If the kit is NOT installed,
and low ambient is selected, low pressure faults and
compressor damage may occur.
OPTION 4 – LOCAL/
REMOTE CONTROL TYPE:
When programmed for LOCAL, an ISN or RCC control
can be used to monitor only. The micro panel will operate
on locally programmed values and ignore all commands
from the remote devices. The chiller will communicate
and send data to the remote monitoring devices.
or
This mode should be selected when an ISN or RCC
control is to be used to control the chiller. This mode will
allow the ISN to control the following items: Remote
Start/Stop, Cooling Setpoint, Load Limit, and History
Buffer Request. If the unit receives no valid ISN trans
-
mission for 5 minutes, it will revert back to the locally
programmed values.
OPTION 6 – UNIT CONTROL MODE:
Unit control is based on Suction Pressure Control.
or
Unit control is based on Discharge Air Temp. Control.
L O C A L / R E M O T E M O D E
R E
M
O T E
A M B I E N T C O N T R O L
L O
W A
M
B I E N T
L O C A L / R E M O T E M O D E L
L O
C A L
C O N T R O L M O D E
S U C T I O N P R E S S U R E
C O N T R O L M O D E
D I S C H A R G E A I R
A M B I E N T C O N T R O L
S T A N D A R D
2
OPTION 6 – DISPLAY UNITS:
This mode displays system operating values in Imperial
units of °F or PSIG.
or
This mode displays system operating values in Scientific
International Units of °C or BARG.
OPTION 7 - LEAD/LAG TYPE (two system units
with Discharge Air Temp Control only):
SYS 1 selected as lead compressor. SYS 1 lead option
MUST be chosen if Hot Gas Bypass is installed.
or
SYS 2 selected as lead compressor.
or
Lead/lag between systems may be selected to help equal-
ize average run hours between systems on chillers with
2 refrigerant systems. Auto lead/lag allows automatic
lead/lag of the two systems based on an average run
hours of the compressors in each system. A new lead/
lag assignment is made whenever all compressors shut
down. The micro will then assign the “lead” to the sys-
tem with the shortest average run time.
OPTION 8 - CONDENSER FAN CONTROL MODE
(YCUL0045-0275 Only):
Condenser fans are controlled by discharge pressure
only. This mode may only be chosen when discharge
pressure transducers are installed.
D I S P L A Y U N I T S
I M
P E R I A L
D I S P L A Y U N I T S
S I
L E A D / L A G C O N T R O L
M A N U A L S Y S 1 L E A D
L E A D / L A G C O N T R O L
M A N U A L S Y S 2 L E A D
L E A D / L A G C O N T R O L
A U T O
M
A T I C
F A N C O N T R O L
D I S C H A R G E P R E S S U R E
Summary of Contents for YCUL0045
Page 13: ...JOHNSON CONTROLS 13 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 35: ...JOHNSON CONTROLS 35 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 71: ...JOHNSON CONTROLS 71 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 79: ...JOHNSON CONTROLS 79 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 117: ...JOHNSON CONTROLS 117 FORM 150 63 NM6 1020 2 This page intentionally left blank...
Page 120: ...JOHNSON CONTROLS 120 FORM 150 63 NM6 1020 Unit Controls THIS PAGE INTENTIONALLY BLANK...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM6 1020 3 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 63 NM6 1020 4 LD08801...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 63 NM6 1020 4 LD08946...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 63 NM6 1020 4 LD08800...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 63 NM6 1020 4 LD08776...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 63 NM6 1020 4 LD08804...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 63 NM6 1020 4 LD08781...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 63 NM6 1020 4 LD08803...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 63 NM6 1020 4 LD08807...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 63 NM6 1020 4 LD08785...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 63 NM6 1020 4 LD08806...