22
BAS/EMS DISCHARGE AIRTEMPERATURE RESET
USING A VOLTAGE OR CURRENT SIGNAL
The Remote Reset Option allows the Control Center of the
unit to reset the discharge air temperature setpoint using a
0 - 10VDC input, or a 4-20mA input connected to
XTBC1 terminals A- and A+. Whenever a reset is called
for, the change may be noted by pressing the Cooling
Setpoints key twice. The new value will be displayed
as “REM SETP = XXX °F.”
If a
0 - 10VDC
signal is supplied, it is applied to terminals
A+ and A-, and
jumper JP1 on the I/O board must be
inserted between pins 2 and 3.
To calculate the reset
discharge air temperature setpoint for values between
0VDC and 10VDC use the following formula:
Setpoint = Local Discharge Air Temp Se °Reset
°
Reset =
(DC voltage signal) x (*Max Reset Value)
10
Example:
Local Discharge Air Temp Setpoint = 45 °F (7.22 °C)
*Max Reset Value = 20 °F (11.11 °C)
Input Signal = 6VDC
(English)
°
Reset =
6VDC x 20 °F
= 12
°F Reset
10
New Setpoint = 45 °F + 12 °F = 57 °F
(Metric)
°
Reset =
6VDC x 11. 11 °C = 6.67 °C Reset
10
New Setpoint = 7.22 °C + 6.67 °C = 13.89 °C
* Max Reset Value is the “Max EMS-PWM Remote Temp. Reset” setpoint
value described in the program ming section under Cooling Setpoints.
Programmable values are from 2 °F to 40 °F (1.11 °C to 11.11
°C).
Note: The suction pressure setpoints can not be reset using a
remote option.
If a
4-20mA signal is supplied,
it is applied to terminals
A+ and A- and
jumper JP1 on the I/O board must be
installed between pin 1 and 2
. To calculate the dis-
charge air temp setpoint for values between 4mA and
20 mA use the following formula:
Setpoint = Local Discharge Air Temp Se °Reset
°Reset = (mA signal - 4) x (*Max Reset Value
)
16
Example:
Local Chilled Liquid Setpoint = 45° (7.22 °C)
*Max Reset Value = 10 °F (5.56 °C)
Input Signal = 12 mA
(English)
°Reset = 8mA x 10 °F = 5 °F Reset
16
Setpoint = 45 °F + 5 °F = 50 °F
(Metric)
°Reset = 8mA x 5.56 °C = 2.78 °C Reset
16
Setpoint = 7.22 °C + 2.78 °C = 10.0 °C
A 240-24 Volt Ratio Transformer (T3) is used to
derive nominal 12 volt output from the 120 volt
supply.
A 240-24 Volt Ration Transformer (T3)
is used to derive nominal 12 output from
the 120 volt supply.
Summary of Contents for YCUL0045
Page 13: ...JOHNSON CONTROLS 13 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 35: ...JOHNSON CONTROLS 35 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 71: ...JOHNSON CONTROLS 71 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 79: ...JOHNSON CONTROLS 79 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 117: ...JOHNSON CONTROLS 117 FORM 150 63 NM6 1020 2 This page intentionally left blank...
Page 120: ...JOHNSON CONTROLS 120 FORM 150 63 NM6 1020 Unit Controls THIS PAGE INTENTIONALLY BLANK...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM6 1020 3 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 63 NM6 1020 4 LD08801...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 63 NM6 1020 4 LD08946...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 63 NM6 1020 4 LD08800...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 63 NM6 1020 4 LD08776...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 63 NM6 1020 4 LD08804...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 63 NM6 1020 4 LD08781...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 63 NM6 1020 4 LD08803...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 63 NM6 1020 4 LD08807...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 63 NM6 1020 4 LD08785...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 63 NM6 1020 4 LD08806...