UNIT OPERATION
2
CAPACITY CONTROL
To initiate the start sequence of the unit, all run per-
missive inputs must be satisfied (air proving/remote
start/stop switch), and no unit or system faults exist.
The first phase of the start sequence is initiated by the
Daily Schedule Start or a Remote Cycling Device. If
the unit is shut down on the daily schedule, the evapo-
rator blower contacts (Terminals 23 and 24 of CTB2)
will close when the daily schedule start time has been
reached. Once the air proving switch closes, capacity
control functions are initiated.
If unit cycling is accomplished with a remote cycling
device wired in series with the air proving switch, the
evaporator contacts will always be energized as long
as the unit switch is turned on. When the air proving
switch and remote cycling contacts are closed, the
capacity control functions will be initiated.
It should be noted that the evaporator contacts (Termi-
nals 23 and 24 of CTB2) are not required to be used to
cycle the evaporator blower. However, in all cases the air
proving switch must be closed to allow unit operation.
The control system will evaluate the need for cooling
by comparing the actual discharge air temperature or
suction pressure(s) to the desired setpoint, and regulate
the discharge air temperature or suction pressure to meet
that desired setpoint.
DISCHARGE AIR TEMPERATURE CONTROL
The setpoint in Discharge Air Temperature Control is the
temperature the condensing unit will control to /-
the control range. The setpoint High Limit is the Setpoint
plus the Cooling Range. The Setpoint Low Limit is the
Setpoint minus the Cooling Range. See Figure 15.
If the Discharge Air Temperature is above the Setpoint
High Limit, the lead compressor on the lead system will
be energized along with the liquid line solenoid. Upon
energizing any compressor, the 60 second Anti-Coin-
cidence timer will be initiated.
If after 180 seconds of run time the discharge air tem-
perature is still above the Setpoint High Limit, the next
compressor in sequence will be energized. Additional
loading stages are energized at a rate of once every 180
seconds if the discharge air temperature remains above
the Setpoint High Limit.
If the discharge air temperature falls below the Setpoint
High Limit but is greater than the Setpoint Low Limit,
loading and unloading do not occur. This area of control
is called the control range.
If the discharge air temperature drops below the Setpoint
Low Limit, unloading occurs at a rate of 60 seconds.
The sequences of Capacity Control (compressor stag-
ing) for loading and unloading are shown in Table 22
through Table 23.
FIG. 15 –
DISCHARGE AIR TEMPERATURE CONTROL
20 sec.
30 sec.
60 sec.
control range 60 sec.
unloading
unloading
unloading
(no compressor staging) loading
51.5°F
52.5°F
53.0°F
55.0°F
57.0°
(10.8°C) (11.4°C) (11.7°C) (12.8°C) (13.9°C)
Low Limit Setpoint High limit
Discharge Air Temperature Control – Compressor Staging
Setpoint = 55.0°F (12.8°C) Range = +/- 5°F (-12.2°C)
Summary of Contents for YCUL0045
Page 13: ...JOHNSON CONTROLS 13 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 35: ...JOHNSON CONTROLS 35 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 71: ...JOHNSON CONTROLS 71 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 79: ...JOHNSON CONTROLS 79 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 117: ...JOHNSON CONTROLS 117 FORM 150 63 NM6 1020 2 This page intentionally left blank...
Page 120: ...JOHNSON CONTROLS 120 FORM 150 63 NM6 1020 Unit Controls THIS PAGE INTENTIONALLY BLANK...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM6 1020 3 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 63 NM6 1020 4 LD08801...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 63 NM6 1020 4 LD08946...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 63 NM6 1020 4 LD08800...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 63 NM6 1020 4 LD08776...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 63 NM6 1020 4 LD08804...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 63 NM6 1020 4 LD08781...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 63 NM6 1020 4 LD08803...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 63 NM6 1020 4 LD08807...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 63 NM6 1020 4 LD08785...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 63 NM6 1020 4 LD08806...