JOHNSON CONTROLS
107
FORM 150.63-NM6 (1020)
Also see the UNIT KEYS PROGRAMMING QUICK
REFERENCE LIST in Table 21, Page 108.
CLOCK
The CLOCK display shows the current day, time, and
date. Pressing the CLOCK key will show the current
day, time, and date.
It is important that the date and time be correct, otherwise the
daily schedule will not function as desired if programmed. In
addition, for ease of troubleshooting via the History printouts,
the day, time, and date should be correct.
To change the day, time, and date press the CLOCK
key. The display will show something similar to the
following:
The line under the F is the cursor. If the day is correct,
press the ENTER/ADV key. The cursor will move under
the 0 in 08 hours. If the day is incorrect, press the UP
or DOWN
arrow keys until the desired day is displayed
and then press the ENTER/ADV key at which time the
day will be accepted and the cursor will move under
the first digit of the “2 digit hour”. In a similar manner,
the hour, minute, meridian, month, day, and year may
be programmed, whenever the cursor is under the first
letter/numeral of the item. Press the UP or DOWN ar-
row keys until the desired hour, minute, meridian, day,
month, and year are displayed. Pressing the ENTER/
ADV Key will save the valve and move the cursor on
to the next programmable variable.
Jumper J11 on the microboard must
be set to the “CLKON” position to turn
on the clock. If this is not done, the
clock will not function.
OPTION 12 – UNIT TYPE:
The UNIT TYPE message cannot be modified under
the unit keys.
“CONDENSING UNIT” must be
displayed, or damage to compressors
or other components will occur if op-
erated in the HEAT PUMP or LIQUID
CHILLER modes.
If unit type needs to be changed to make the unit
a condensing unit, add a jumper between J4-6 and
J4-11, of the microboard and reapply power to the
micropanel.
OPTION 13 – REFRIGERANT TYPE:
Refrigerant type R-22 or R-407C may be selected un-
der Service Mode. Refrigerant type is displayed under
the Options Key, but is only programmable in Service
Mode.
Incorrect programming may cause
damage to compressors.
OPTION 14 – EXPANSION VALVE TYPE:
Expansion valve type, thermostatic or electronic
may be selected under Service Mode. Expansion valve
type is displayed under the Options key, but is only
programmable in Service Mode.
Incorrect programming may cause
damage to compressors. This must be
programmed for "Thermostatic".
2
U N I T T Y P E
C O N D E N S I N G U N I T
R E F R I G E R A N T T Y P E
R - 2 2
E X P A N S I O N V A L V E T Y P E
T H E R M O S T A T I C
T O D A Y I S F R I 0 8 : 5 1 A M
2 5 J A
N 0 2
S O F T S T A R T
D I S A B L E D
This MUST be selected on all chillers without the soft
start option.
Summary of Contents for YCUL0045
Page 13: ...JOHNSON CONTROLS 13 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 35: ...JOHNSON CONTROLS 35 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 71: ...JOHNSON CONTROLS 71 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 79: ...JOHNSON CONTROLS 79 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 117: ...JOHNSON CONTROLS 117 FORM 150 63 NM6 1020 2 This page intentionally left blank...
Page 120: ...JOHNSON CONTROLS 120 FORM 150 63 NM6 1020 Unit Controls THIS PAGE INTENTIONALLY BLANK...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM6 1020 3 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 63 NM6 1020 4 LD08801...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 63 NM6 1020 4 LD08946...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 63 NM6 1020 4 LD08800...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 63 NM6 1020 4 LD08776...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 63 NM6 1020 4 LD08804...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 63 NM6 1020 4 LD08781...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 63 NM6 1020 4 LD08803...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 63 NM6 1020 4 LD08807...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 63 NM6 1020 4 LD08785...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 63 NM6 1020 4 LD08806...