JOHNSON CONTROLS
115
FORM 150.63-NM6 (1020)
2
FIG. 17 –
YCUL0045 – YCUL0275 FAN LOCATION (TYPICAL)
LD07403
CONDENSER FAN CONTROL - YCUL0045 – YCUL0275
TABLE 26 –
YCUL0045 – YCUL0275 CONDENSER FAN CONTROL USING OUTDOOR AMBIENT TEMPERA-
TURE AND DISCHARGE PRESSURE (DISCHARGE PRESSURE CONTROLS WILL NOT FUNC-
TION UNLESS THE OPTIONAL DISCHARGE PRESSURE TRANSDUCER IS INSTALLED)
CONTACTOR
MICRO BOARD
FAN #
FAN STAGE
ON
OFF
OUTPUT TB-4
SYS 1 SYS 2
SYS 1 SYS 2
SYS 1 SYS 2
1
OAT >25°F (-3.9°C)
OAT < 20°F (-6.7°C)
1 FAN FWD
OR
AND
8M 11M
4 8
3 4
DP > Fan Ctrl On Press
DP < Fan Ctrl On Press – (Diff. Press.)
*3
OAT >65°F (18.3°C)
OAT < 60°F (15.6°C)
2 FAN FWD
OR
AND
7M & 10M &
2 & 4 6 & 8
1 & 3 2 & 4
DP > Fan Ctrl On Press
DP < Fan Ctrl On Press –
8M
11M
+ 40 PSIG (2.76 Bars)
[Diff. Press + 40 PSIG (2.76 Bars)]
TABLE 27 –
YCUL0045 – YCUL0275 CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY
CONTACTOR
MICRO BOARD
FAN #
FAN STAGE
ON
OFF
OUTPUT TB-4
SYS 1 SYS 2
SYS 1 SYS 2
SYS 1 SYS 2
1
DP > Fan Ctrl On Press DP < Fan Ctrl On Press – (Diff. Press.)
8M 11M
4 8
3 4
1 FAN FWD
*3
DP > Fan Ctrl On Press +
DP < Fan Ctrl On Press –
7M & 10M &
2 & 4 6 & 8
1 & 3 2 & 4
2 FANS FWD
40 PSIG (2.76 Bars)
[(Diff. Press.) + 40 PSIG (2.76 Bars)]
8M
11M
* NOTE:
STEP 2 is not active in the “Standard Ambient” mode. When changing to “Low Ambient” control, fan power wiring also changes.
Fan #1
Fan #2
Fan #3
Fan #4
Summary of Contents for YCUL0045
Page 13: ...JOHNSON CONTROLS 13 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 35: ...JOHNSON CONTROLS 35 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 71: ...JOHNSON CONTROLS 71 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 79: ...JOHNSON CONTROLS 79 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 117: ...JOHNSON CONTROLS 117 FORM 150 63 NM6 1020 2 This page intentionally left blank...
Page 120: ...JOHNSON CONTROLS 120 FORM 150 63 NM6 1020 Unit Controls THIS PAGE INTENTIONALLY BLANK...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM6 1020 3 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 63 NM6 1020 4 LD08801...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 63 NM6 1020 4 LD08946...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 63 NM6 1020 4 LD08800...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 63 NM6 1020 4 LD08776...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 63 NM6 1020 4 LD08804...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 63 NM6 1020 4 LD08781...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 63 NM6 1020 4 LD08803...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 63 NM6 1020 4 LD08807...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 63 NM6 1020 4 LD08785...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 63 NM6 1020 4 LD08806...