JOHNSON CONTROLS
106
FORM 150.63-NM6 (1020)
OPTION 9 – MANUAL OVERRIDE MODE:
This option allows overriding of the daily schedule that
is programmed. MANUAL OVERRIDE MODE – DIS
-
ABLED indicates that override mode has no effect.
or
Manual Override Mode is enabled. This is a service
function and when enabled, will allow the unit to start
when shut down on the daily schedule. It will auto-
matically be disabled after 30 minutes.
OPTION 10 – CURRENT FEEDBACK OPTIONS
INSTALLED:
This mode should be selected when the panel is not
equipped with current sensing capability.
or
This mode should be selected when an optional 2ACE
Module is installed to allow combined current moni-
toring of all systems by sensing current on the incoming
line. Current input is to J8-5 of the micro.
or
This mode should be selected when an optional 2ACE
module is installed to allow individual current mon-
itoring of each system. SYS 1 input is to J8-5 of the
micro. SYS 2 input is to J8-6 of the micro.
OPTION 11 – SOFT START ENABLE/DISABLE:
Unit Controls
S O F T S T A R T
E N A B L E D
C U R R E N T F E E D B A C K
N
O
N
E
C U R R E N T F E E D B A C K
O N E P E R U N I T
C U R R E N T F E E D B A C K
O N E P E R S Y S T E M
M A N U A L O V E R R I D E M O D E
D I S A B L E D
M A N U A L O V E R R I D E M O D E
E N A B L E D
F A N C O N T R O L
A M B I E N T & D S C H P R E S S
Condenser fans are controlled by ambient temperature
and discharge pressure. This mode must be chosen if the
discharge pressure transducers are
not
installed.
x
x
1
1
x = Compressors
with soft start
YCUL0125-0185
Control Panel End
This should only be enabled on European units with soft
start on 2 compressors. This feature modifies the com
-
pressor lead/lag to start the compressor(s) furthest from
the control panel last to minimize current inrush. These
compressors will be equipped with a soft starter.
Soft start is only viewable under OP-
TIONS key and must be programmed
from the Service Mode.
On 2 compressor chillers, soft start will always be ap-
plied to the compressor farthest from the control panel.
This compressor will always start last to minimize cur-
rent inrush with the other compressor running.
On 4 compressor chillers, soft start will always be ap-
plied to the compressor furthest from the control panel
on each system. These compressors will always start last
to minimize current inrush with the other compressors
running.
On 6 compressor chillers, soft start will always be ap-
plied to the compressors farthest from the control panel
on each system. Compressors 1 and 2 of each system will
continue to lead/lag per the selected option. The soft start
compressors will always start last to minimize current
inrush with the other compressors running.
x = Compressors
with soft start
Control Panel End
YCUL0211-0275
x
2
1
x
2
1
Summary of Contents for YCUL0045
Page 13: ...JOHNSON CONTROLS 13 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 35: ...JOHNSON CONTROLS 35 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 71: ...JOHNSON CONTROLS 71 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 79: ...JOHNSON CONTROLS 79 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 117: ...JOHNSON CONTROLS 117 FORM 150 63 NM6 1020 2 This page intentionally left blank...
Page 120: ...JOHNSON CONTROLS 120 FORM 150 63 NM6 1020 Unit Controls THIS PAGE INTENTIONALLY BLANK...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM6 1020 3 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 63 NM6 1020 4 LD08801...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 63 NM6 1020 4 LD08946...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 63 NM6 1020 4 LD08800...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 63 NM6 1020 4 LD08776...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 63 NM6 1020 4 LD08804...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 63 NM6 1020 4 LD08781...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 63 NM6 1020 4 LD08803...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 63 NM6 1020 4 LD08807...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 63 NM6 1020 4 LD08785...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 63 NM6 1020 4 LD08806...