FORM 150.63-NM6 (1020)
TROUBLESHOOTING
PROBLEM
CAUSE
SOLUTION
No display on panel.
1. No 115VAC to 1T.
1a. Check wiring and fuse
Unit will not operate.
3FU
b. Check wiring emergency
stop contacts 5 to L of CTB2
Terminal
Block.
c. Replace 1T
2. No 24VAC to Microboard
2. Check wiring 1T to
Microboard.
3. 1T defective, no
3. Replace 1T
24VAC output.
4. Short in wire to temp. sensors
4. Unplug connections at
or pressure transducers.
Microboard to isolate.
5. Defective Microboard
5. Replace Microboard.
or Display board.
NOTE: Contact YORK
Service
before
Replacing circuit Boards!
“FLOW SWITCH/REM
1. No air flow.
1. Check air flow.
STOP NO RUN PERMISSIVE”
2. Air flow switch improperly
2. Check that the air flow switch
installed.
is installed according to
manufacturer’s
instructions.
3. Defective air flow switch.
3. Replace air flow switch.
4. Remote cycling device open.
4. Check cycling devices
connected to terminals
13 and 14 of the CTB1
Terminal
Block.
“LOW SUCTION PRESSURE”
1. Improper suction pressure
1. Adjust per recommended
FAULT
cutouts adjustments.
settings.
2. Low refrigerant charge.
2. Repair leak if necessary
and add refrigerant.
3. Fouled filter dryer.
3. Change dryer/core.
TABLE 38 –
TROUBLESHOOTING
CONT’D
Service and Troubleshooting
Summary of Contents for YCUL0045
Page 13: ...JOHNSON CONTROLS 13 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 35: ...JOHNSON CONTROLS 35 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 71: ...JOHNSON CONTROLS 71 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 79: ...JOHNSON CONTROLS 79 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 117: ...JOHNSON CONTROLS 117 FORM 150 63 NM6 1020 2 This page intentionally left blank...
Page 120: ...JOHNSON CONTROLS 120 FORM 150 63 NM6 1020 Unit Controls THIS PAGE INTENTIONALLY BLANK...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM6 1020 3 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 63 NM6 1020 4 LD08801...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 63 NM6 1020 4 LD08946...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 63 NM6 1020 4 LD08800...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 63 NM6 1020 4 LD08776...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 63 NM6 1020 4 LD08804...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 63 NM6 1020 4 LD08781...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 63 NM6 1020 4 LD08803...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 63 NM6 1020 4 LD08807...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 63 NM6 1020 4 LD08785...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 63 NM6 1020 4 LD08806...