![background image](http://html1.mh-extra.com/html/york/ycul0045/ycul0045_installation-operation-and-maintenance_4223634130.webp)
JOHNSON CONTROLS
130
FORM 150.63-NM6 (1020)
.
TABLE 37 –
KEYPAD PIN ASSIGNMENT MATRIX
KEYPAD
PIN CONNECTIONS
STATUS
1 TO 5
OPER DATA
1 TO 7
1 TO 6
HISTORY
1 TO 8
UP ARROW
2 TO 5
DOWN ARROW
2 TO 7
ENTER/ADV
2 TO 6
COOLING SETPOINTS
2 TO 8
SCHEDULE/ADVANCE DAY
3 TO 5
PROGRAM
3 TO 7
OPTIONS
3 TO 6
CLOCK
3 TO 8
KEYPAD
The operator keypad is connected to the microboard
by a ribbon cable, which is connected to J2 on the mi-
croboard.
The integrity of a specific “button” on the keypad can be
verified by doing a continuity check across two specific
points (or pins), that represent one of twelve “buttons”
on the keypad.
Table 37 lists the key/pin assignments for the keypad.
Power to the microboard must be turned off, and
the ribbon cable disconnected from the microboard
prior to conducting the tests, or component damage
may result.
After the ribbon cable is disconnected from microboard,
ohmmeter leads are connected to the pins representing
the specific “button” to be tested. After connecting the
meter leads, the “button” being checked is pressed
and a reading of zero ohms should be observed. After
releasing the “button,” the resistance value should be
infinite (open circuit).
Pin 1 is usually identified by a stripe
on the ribbon cable.
Service and Troubleshooting
Summary of Contents for YCUL0045
Page 13: ...JOHNSON CONTROLS 13 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 35: ...JOHNSON CONTROLS 35 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 71: ...JOHNSON CONTROLS 71 FORM 150 63 NM6 1020 1 This page intentionally left blank...
Page 79: ...JOHNSON CONTROLS 79 FORM 150 63 NM6 1020 This page intentionally left blank...
Page 117: ...JOHNSON CONTROLS 117 FORM 150 63 NM6 1020 2 This page intentionally left blank...
Page 120: ...JOHNSON CONTROLS 120 FORM 150 63 NM6 1020 Unit Controls THIS PAGE INTENTIONALLY BLANK...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM6 1020 3 This page intentionally left blank...
Page 141: ...JOHNSON CONTROLS 141 FORM 150 63 NM6 1020 4 LD08801...
Page 145: ...JOHNSON CONTROLS 145 FORM 150 63 NM6 1020 4 LD08946...
Page 147: ...JOHNSON CONTROLS 147 FORM 150 63 NM6 1020 4 LD08800...
Page 151: ...JOHNSON CONTROLS 151 FORM 150 63 NM6 1020 4 LD08776...
Page 153: ...JOHNSON CONTROLS 153 FORM 150 63 NM6 1020 4 LD08804...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 63 NM6 1020 4 LD08781...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 159: ...JOHNSON CONTROLS 159 FORM 150 63 NM6 1020 4 LD08803...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 63 NM6 1020 4 LD08807...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 63 NM6 1020 4 LD08785...
Page 165: ...JOHNSON CONTROLS 165 FORM 150 63 NM6 1020 4 This page intentionally left blank...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 63 NM6 1020 4 LD08806...