7.2.13 Setting VT Ratio (
)
Description
When installing an external voltage transformer (VT) and inputting the
secondary-circuit output of the VT to the CW120/121, setting the VT ratio
appropriately will display the reading correctly in the scale of the primary
circuit, namely, will perform scaling.
The VT ratio can be set from 1 to 10000 and is set to 1 by default.
When not using a VT, set the VT ratio to 1.
Whenever the VT ratio is set to a value other than 1, the
mark is displayed
even in the measurement mode.
Procedure
(1) Using the
keys in the setting item selection screen, make the
mark and the existing VT ratio setting appear on the screen. Then,
press the
key. The digit of the one place flashes.
DISP
ENTER
MEAS/SET
ESC
MEAS/SET key
UP/DOWN/LEFT/RIGHT keys
ENTER key
ESC key
VT Ratio = 1
VT Ratio = 10000
(2) Using the
keys, select the digit to be changed. The selected digit
flashes.
(3) Using the
keys, change the number.
(4) After making necessary changes, press the
key. The VT ratio
setting is changed accordingly and the setting item selection screen
returns.
To cancel the changes, press the
key. The setting item selection
screen also returns.