7-24
IM CW120-E
7.2.14 Setting CT Ratio (
)
Description
When installing an external current transformer (CT) and inputting the
secondary-circuit output of the CT to the CW120/121, setting the CT ratio
appropriately will display the reading correctly in the scale of the primary
circuit, namely, will perform scaling.
The CT ratio can be set from 1.00 to 10000.0 and is set to 1.00 by default.
When not using a CT, set the CT ratio to 1.00.
Whenever the CT ratio is set to a value other than 1.00, the
mark is
displayed even in the measurement mode.
Procedure
(1) Using the
keys in the setting item selection screen, make the
mark and the existing CT ratio setting appear on the screen. Then,
press the
key. The digit of the one place flashes.
DISP
ENTER
MEAS/SET
ESC
MEAS/SET key
UP/DOWN/LEFT/RIGHT keys
ENTER key
ESC key
CT Ratio = 1.00
CT Ratio = 10000.0
(2) Using the
keys, select the digit to be changed. The selected digit
flashes.
(3) Using the
keys, change the number.
(4) After making necessary changes, press the
key. The CT ratio
setting is changed accordingly and the setting item selection screen
returns.
To cancel the changes, press the
key. The setting item selection
screen also returns.
7.2 Setting Each Item