<Appendix 5. PID Block>
280
IM 01E21A02-03EN
A5.3 Parameter List of PID Block
A blank in the Write Mode column indicates that the corresponding parameter can be written in all
modes.
Index
Parameter
Name
Default
Value
Write
mode
Valid
Range
Description
0
Block Header
TAG:
“PID”
Block Tag
= O/S
Same as that for the AI block.
1
ST_REV
---
Same as that for the AI block.
2
TAG_DESC
Null
Same as that for the AI block.
3
STRATEGY
1
Same as that for the AI block.
4
ALERT_KEY
1
1 to 255
Same as that for the AI block.
5
MODE_BLK
6
BLOCK_ERR
---
Same as that for the AI block.
7
PV
---
Measured value; Non-dimensional value
that is converted from the input (IN) value
based on the PV_SCALE values and
filtered.
8
SP
0
AUTO
PV_SCALE
±10%
Setpoint
9
OUT
Man
Output value.
10
PV_SCALE
100
0
1133
1
O/S
Scale conversion value for the input (IN)
value.
11
OUT_SCALE
100
0
1342
1
O/S
Scale values used for converting the control
output (OUT) value to actual amount.
12
GRANT_DENY
0
AUTO
Same as that for the AI block.
13
CONTROL_
OPTS
0
O/S
Defines settings for control action.
See Subsection A5.13.1 for details.
14
STATUS_OPTS
0
O/S
See Subsection A5.15.3 for details.
15
IN
0
Measurement input
16
PV_FTIME
2
AUTO
non
negative
Time constant (in seconds) of the first-order
lag filter applied to measurement input
17
BYPASS
1 (OFF)
Man
1, 2
Switch whether to set the BYPASS
operation; set ON to bypass the control
operation.
18
CAS_IN
0
Cascade setpoint
19
SP_RATE_DN
+INF
Positive
Rate-of-decrease limit for setpoint (SP)
20
SP_RATE_UP
-INF
Positive
Rate-of-increase limit for setpoint (SP)
21
SP_HI_LIM
100
PV_SCALE
±10%
Upper limit for setpoint (SP)
22
SP_LO_LIM
0
PV_SCALE
±10%
Lower limit for setpoint (SP)
23
GAIN
1
Proportional gain
24
RESET
10
Integration time (seconds)
25
BAL_TIME
0
Positive
Unused
26
RATE
0
Positive
Derivative time (seconds)
27
BKCAL_IN
0
Read-back of control output
28
OUT_HI_LIM
100
OUT_
SCALE
±10%
Upper limit for control output (OUT)
29
OUT_LO_LIM
0
OUT_
SCALE
±10%
Lower limit for control output (OUT)
30
BKCAL_HYS
0.5(%)
0 to 50%
Hysteresis for release from a limit for OUT.
status
31
BKCAL_OUT
0
---
Read-back value to be sent to the BKCAL_
IN in the high-level block