<3. Getting Started>
19
IM 01E21A02-03EN
3.3 Bus Power ON
Turn on the power of the host, the bus, and this product. If this product is equipped with a display,
first all segments are lit, and then the display begins to operate. If the display is not turned on, or
abnormal current flows, check the polarity of power.
Using the host device display function, check that this product is in operation on the bus.
The device information, including the PD tag, Node address, and Device ID, is described on
the sheet (see Figure 3.3) attached to the device. The same device information is given at two
locations on this sheet.
Device ID
:
5945430016XXXXXXXX
PD Tag
: FT2001
Device Revision
:
1
Node Address
:
0xF4
Serial No.
:
XXXXXXXXXXXXXXXXX
Physical Location :
Note:
Our Device Description Files and Capabilities Files available at
http://www.yokogawa.com/fld/ (English) or
http://www.yokogawa.co.jp/fld/ (Japanese)
Device ID
:
5945430016XXXXXXXX
PD Tag
: FT2001
Device Revision
:
1
Node Address
:
0xF4
Serial No.
:
XXXXXXXXXXXXXXXXX
Physical Location :
Note:
Our Device Description Files and Capabilities Files available at
http://www.yokogawa.com/fld/ (English) or
http://www.yokogawa.co.jp/fld/ (Japanese)
F0303.ai
Figure 3.3
Device Information Attached to This Product.
If this product is not detected, check the address range in use and the polarity of power. If the
node address and PD tag are not specified when ordering, the default value (0xF4) is factory set.
If two or more devices with the same node address are connected at the same time, one device
retains its factory-set address, while the other devices have default addresses of 0xF8 or later. In
such a case, set an individual address.