<5. Functions>
56
IM 01E21A02-03EN
Display
Device setup ► Detailed setup ► Totalizer ► (see below)
F
OUNDATION
Fieldbus
Device Configuration ► STB ► Device Configuration ► Configuration ► Totalizer ► (see
below)
Block
Name
Relative
Index
Parameter
Description
Display
F
OUNDATION
Fieldbus
STB
67
Totalizer 1 ► Unit
Totalizer 1 ► Total 1 Lowcut
Displays the unit of totalizer 1.
STB
76
Totalizer 2 ► Unit
Totalizer 2 ► Total 2 Lowcut
Displays the unit of totalizer 2.
NOTE
If there is inconsistency between the process value selected in the AI FB channel and the unit set
with XD scale Units index, Bit1 in Block Error of the AI function block is set on.
Example:
AI Channel: 2 (volumetric flow rate), XD scale Units index (Transducer Scale.Units Index): 1328
(t/h)
5.1.5 Span Setting
The flow velocity, volumetric flow rate, mass flow rate, and calorie can be set from Sensor TB.
However, the unit of the span is the unit set in Subsection 5.1.4.
If the flow rate unit is changed, the span value is converted in conjunction with the changed unit.
The setting can be configured with the following parameters.
Flow velocity, volumetric flow rate, mass flow rate, calorie
Menu path
Display
Device setup ► Detailed setup ► Pro var ► (see below)
F
OUNDATION
Fieldbus
Device Configuration ► STB ► Device Configuration ► Configuration ► Process
Variables ► (see below)
Block
Name
Relative
Index
Parameter
Description
Display
F
OUNDATION
Fieldbus
STB
62
Velocity ► Span
Velocity ► Velocity Span
Specifies the span of the flow
velocity.
STB
63
Volume ► Span
Volume Flow ► Volume Flow
Span
Specifies the span of
volumetric flow rate.
STB
64
Mass ► Span
Mass Flow ► Mass Flow Span Specifies the span of the mass
flow rate.
STB
65
Calorie ► Span
Calorie ► Calorific Span
Specifies the span of the
calorie.
(Only available for AXG, not for
AXW).