<5. Functions>
60
IM 01E21A02-03EN
Frequency output/pulse output
Menu path
Display
Device setup ► Detailed setup ► Pulse/Status out ► PO1/SO1 ► (see below)
F
OUNDATION
Fieldbus
Device Configuration ► MTB ► Device Configuration ► Maintenance ► Pulse/Status Out
► (see below)
Block
Name
Relative
Index
Parameter
Description
Display
F
OUNDATION
Fieldbus
MTB
107
Low cut
Pulse 1 Low Cut
Specifies the low-cut value of
the frequency output and pulse
output.
Totalizer
Menu path
Display
Device setup ► Detailed setup ► Totalizer ► (see below)
F
OUNDATION
Fieldbus
Device Configuration ► STB ► Device Configuration ► Configuration ► Totalizer► (see
below)
Block
Name
Relative
Index
Parameter
Description
Display
F
OUNDATION
Fieldbus
STB
67
Totalizer 1 ► Low cut Totalizer 1 ► Total 1 Lowcut
Specifies the low-cut value of
totalizer 1.
STB
76
Totalizer 2 ► Low cut Totalizer 2 ► Total 2 Lowcut
Specifies the low-cut value of
totalizer 2.
An actual value which makes low cutting effective has ± 0.5% hysteresis from the set low-
cut value. The hysteresis width on the negative side (going into the low cut when flow rate is
decreasing) and the positive side (going out of low cut when flow rate is increasing) are as
follows:
(1) Negative side
= Low-cut setpoint - (Minimum span set with multi range x 0.5%)
(2) Positive side
= Low-cut se (Minimum span set with multi range x 0.5%)
Example: When setting to span of volumetric flow rate = 10.0 m3/h,
Low-cut value = 1.0 m3/h
(1) Negative side
= 1.0 [m
3
/h] – (10.0 [m
3
/h] x 0.5 [%])
= 0.95 [m
3
/h]
(2) Positive side
= 1.0 [m
3
/h] + (10.0 [m
3
/h] x 0.5 [%])
= 1.05 [m
3
/h]