<6. Parameter Lists>
217
IM 01E21A02-03EN
6.8 MAO Function Block (only AXG)
Relative
Index
Index
Parameter
Name
Default Value
Write
Mode
Description
0
10000 Block Header
“MAO”
O/S
Information on this block, such as Block
Tag, DD Revision, Execution, etc.
1
10001 ST_REV
0
-
Represents the revision level of the setting
parameter of the own block. This revision
is updated if the setpoint is changed. Used
to check for parameter change, etc.
2
10002 TAG_DESC
Space (32
characters)
AUTO
Universal parameter to store a comment
explaining tag contents.
3
10003 STRATEGY
1
AUTO
Universal parameter intended to be used
for the high-level system to separate
function blocks.
4
10004
ALERT_KEY
1
AUTO
Key information to identify where an alert
takes place. Generally, this parameter is
used by the high-level system to identify
specific areas in a plant that are under the
control of specific operators, to separate
necessary alerts only. This is one of the
universal parameters.
5
10005
MODE_BLK
0x80(O/S)
0x80(O/S)
0x88(Auto, O/S)
0x08(Auto)
AUTO
-
AUTO
AUTO
Universal parameter to show a block
operation state. Consists of Actual mode,
Target mode, Permit mode and Normal
mode.
6
10006
BLOCK_ERR
0x0000
-
Indicates the error statuses related to the
own block.
7
10007 CHANNEL
20(Temperature)
O/S
Parameter to select a channel for the
transducer block to connect with. For this
product, 20 fixed.
8
10008 IN_1
0x0B
0
AUTO
AUTO
See 5.4.
9
10009 IN_2
0x0B
0
AUTO
AUTO
Not used for this product.
10
10010 IN_3
0x0B
0
AUTO
AUTO
11
10011 IN_4
0x0B
0
AUTO
AUTO
12
10012 IN_5
0x0B
0
AUTO
AUTO
13
10013 IN_6
0x0B
0
AUTO
AUTO
14
10014 IN_7
0x0B
0
AUTO
AUTO
15
10015 IN_8
0x0B
0
AUTO
AUTO
16
10016 MO_OPTS
0x0000
AUTO
Operational parameter to specify the
output operation of MAO Function Block.
Specifies a value to be transmitted to the
sensor transducer block mainly at the fault
state. Bit assignment complies with the
Communication standard specifications.
17
10017 FSTATE_
TIME
0
AUTO
Transits to the fault state when an input
continues to be Bad for more than time set
by FSTATE_TIME.
18
10018 FSTATE_
VAL1
0
AUTO
Value to be transmitted to the sensor
transducer block as input 1 at the fault
state. (Option)
19
10019 FSTATE_
VAL2
0
AUTO
Value to be transmitted to the sensor
transducer block as input 2 at the fault
state. (Option)