<6. Parameter Lists>
171
IM 01E21A02-03EN
Relative
Index
Index
Parameter Name
Default Value
Write
Mode
Description
26
1026
SHED_RCAS
640000
AUTO
Sets time for device’s communication
timeout set for Remote cascade. Used
only with PID function.
27
1027
SHED_ROUT
640000
AUTO
Sets time for device’s communication
timeout set for remote out. Used only
with PID function.
28
1028
FAULT_STATE
1
-
Indicates failsafe state. Not used for this
product.
29
1029
SET_FSTATE
1
AUTO Starts failsafe state. Not used for this
product.
30
1030
CLR_FSTATE
1
AUTO Resets failsafe state. Not used for this
product.
31
1031
MAX_NOTIFY
128
-
Maximum number of alert information
which can be held in the device.
32
1032
LIM_NOTIFY
128
AUTO
Maximum number of alert information
which the device notifies at a time. By
specifying this, the number of alert
to notify the host is limited, and it can
prevent the host from overflowing.
33
1033
CONFIRM_TIME 640000
AUTO
34
1034
WRITE_LOCK
1
AUTO
Prohibits setpoints from being written
from the outside.
1: Not Locked
2: Locked
35
1035
UPDATE_EVT
0(Uninitialized)
0(Uninitialized)
0,0
0
0
AUTO
-
-
-
-
Indicates contents of the event when an
update event (a change to the setpoint)
occurs.
36
1036
BLOCK_ALM
0(Uninitialized)
0(Uninitialized)
0,0
0(Other)
0
AUTO
-
-
-
-
Indicates contents of the alarm when a
block alarm occurs.
37
1037
ALARM_SUM
0x0000
0x0000
0x0000
0x0000
-
-
-
AUTO
Parameter to show the alarm status
of the entire block. Bit assignment
complies with the Communication
standard specifications.
38
1038
ACK_OPTION
0xFFFF
AUTO
Sets operation to acknowledge
(acknowledgment for the alarm) of
various alarms. By setting a bit to the
alarm, the device operates for the
alarm as if it is acknowledged without
the acknowledgment. Bit assignment
complies with the Communication
standard specifications.
39
1039
WRITE_PRI
0
AUTO
Sets the WRITE_ALM priority. It can be
used not just to set the priority, but to
disable alarm notification with settings.
To activate an alarm on communication,
it is necessary to specify the priority for
alarm activation in advance. To activate
an alarm, set 3 or more. By sending with
priority information being added in a
communication frame when the alarm is
activated, for example, the alarm is used
to apply a filter to ignore values below
the specified priority on the host side.
40
1040
WRITE_ALM
0(Uninitialized)
0(Uninitialized)
0,0
0(Other)
0(State 0)
AUTO
-
-
-
-
The alarm is activated if the write lock
condition is changed in the sequence
like, “Lock -> Reset” or “Reset -> Lock”.