<5. Functions>
108
IM 01E21A02-03EN
Alarm record mask
If the alarm record mask function is turned “On”, it disables the alarm record.
Setting example for alarm “Empty pipe detection”:
To disable the alarm record, set “Empty detect on” of STB: Alarm Record Mask2 to “On”.
To enable the alarm record, set “Empty detect on” of STB: Alarm Record Mask2 to “Off”.
Menu path
Display
Device setup ► Diag/Service ► Sts/Self test ► Alarm ► Alarm record mask ► (see below)
F
OUNDATION
Fieldbus
Device Configuration ► STB ► Device Configuration ► Query Device ► SnsrTB Original
Parameters(Part2) ► Page 4 ► Alarm Record Mask ► (see below)
Block
Name
Relative
Index
Parameter
Description
Display
F
OUNDATION
Fieldbus
STB
152
Mask 1-1
Alarm Record Mask1
Specifies the mask function for
alarm record 1-1.
Mask 1-2
Specifies the mask function for
alarm record 1-2.
STB
153
Mask 2-1
Alarm Record Mask2
Specifies the mask function for
alarm record 2-1.
Mask 2-2
Specifies the mask function for
alarm record 2-2.
STB
154
Mask 3-1
Alarm Record Mask3
Specifies the mask function for
alarm record 3-1.
NOTE
Note that an alarm masked with the alarm notification mask function is not recorded in the alarm
record.
The alarm mask function setting is as follows.
Parameter Name
Indicates the name of the mask setting parameter.
Alarm Name
Indicates the alarm name.
Default Value
Indicates the default setting values (at shipment from the manufacturing factory). (
:
Masked, -: Not masked)
Attribute
Indicates whether the mask setting is enabled or disabled. (
: Setting enabled, -: Setting
disabled)
Alarm notification mask function
Display
F
OUNDATION
Fieldbus
Default Value
Attribute
Parameter
Name
Alarm Name
Parameter
Name
Alarm Name
-
010:Main CPU FAIL
-
Main board CPU
failure
-
-
-
011:Rev calc FAIL
-
Reverse calculation
failure
-
-
-
012:Main EEP FAIL
-
Main board EEPROM
failure
-
-
Mask 1-1
013:Main EEP dflt
Alarm out mask 1 Main board EEPROM
default
-
-
014:Snsr bd FAIL
-
Sensor board failure
-
-
-
015:Snsr comm ERR
-
Sensor
communication error
-
-
-
016:AD 1 FAIL[Sig]
-
A/D1 failure[Signal]
-
-
-
017:AD 2 FAIL[Excit]
-
A/D2 failure[Exciter]
-
-