<Appendix 3. Arithmetic (Ar) Block>
264
IM 01E21A02-03EN
Relative
Index Parameter Name
Write
mode
Valid
Range
Default
Value
Description / Remarks
13
INPUT_OPTS
0
Determines whether an input is used as a “good”
input when the input status is “bad” or “uncertain”.
Bit
Function
0
Handles IN as a “good” status input if its
status is “uncertain”.
1
Handles IN_LO as a “good” status input if its
status is “uncertain”.
2
Handles IN_1 as a “good” status input if its
status is “uncertain”.
3
Handles IN_1 as a “good” status input if its
status is “bad”.
4
Handles IN_2 as a “good” status input if its
status is “uncertain”.
5
Handles IN_2 as a “good” status input if its
status is “bad”.
6
Handles IN_3 as a “good” status input if its
status is “uncertain”.
7
Handles IN_3 as a “good” status input if its
status is “bad”.
8 to
15 Reserved
14
IN
0
Input block
15
IN_LO
0
Input for a low-range process value.
This is used for the range extension function.
16
IN_1
0
Auxiliary input 1
17
IN_2
0
Auxiliary input 2
18
IN_3
0
Auxiliary input 3
19
RANGE_HI
0
High limit for switching to a high-range process
value (IN) by the range extension function.
20
RANGE_LO
0
Low limit for switching to a low-range process value
(LO_IN) by the range extension function.
21
BIAS_IN_1
0
IN_1 bias
22
GAIN_IN_1
0
IN_1 gain
23
BIAS_IN_2
0
IN_2 bias
24
GAIN_IN_2
0
IN_2 gain
25
BIAS_IN_3
0
IN_3 bias
26
GAIN_IN_3
0
IN_3 gain
27
COMP_HI_LIM
+INF
High limit of compensation factor f
28
COMP_LO_LIM
-INF
Low limit of compensation factor f