2 Brake Monitoring (Unintended Car Movement)
YASKAWA
TOEPC710616134G AC Drive L1000A Technical Manual Addendum
11
Figure 2.4 Fault during Start (left) and Fault during Stop (right)
Fault Behavior During Run
If at any point during Run the logic state of one of the Brake Feedback inputs changes unexpectedly, a countdown
timer with the value of parameter
S6-06
will be initiated. If the timer expires without change of Brake Feedback
status to its expected state, an
SE4
Fault will be triggered and the fault message
“
Brake Response Error (SE4)
”
will be displayed.
Selected Speed
S1-04
(DC Injection/
Position Lock
Time @ Start
S1-06
(Brake Release
Delay Time)
S1-10
Up/Down Command
Delay Time
Speed
Up/Down
Command
Nominal Speed
Leveling Speed
Brake Control
H2-XX=50h
Brake Feedback 1
H1-XX=79h
Brake Feedback 2
H1-XY=79h
Motor Brake 1
Motor Brake 2
S6-05
SE4 Brake
Monitor Error
EN