3 DI-A3 Option Multi-Functional Support
14
YASKAWA
TOEPC710616134G AC Drive L1000A Technical Manual Addendum
9. Execute test travel.
10. The drive should operate normally.
Repeat this NPN logic procedure for Brake Feedback 2 (e.g. input S8).
■
Function Test PNP Logic
The following steps have to be performed for the functional test after commissioning when using PNP logic:
1. Connect 24 V to Brake Feedback 1 (e.g. input S7).
2. Execute test travel.
3. During start an
SE4
fault should be triggered and the drive should immediately stop.
4. The drive should be blocked and no further travel should be possible even after power cycle.
5. Disconnect 24 V on Brake Feedback 1.
6. Execute test travel.
7. The drive should be blocked and no further travel should be possible even after power cycle.
8. Set
S6-18 = 1
to unlock the drive.
9. Execute test travel.
10. The drive should operate normally.
Repeat this PNP logic procedure for Brake Feedback 2 (e.g. input S8).
■
Brake Feedback
The following steps have to be performed to ensure correct operation of the Brake Feedback switches and
function.
Brake Monitor 1
•
Check if Motor Brake 1 operates correctly.
•
Check status of Motor Switch in Brake 1.
•
Check if the logic changes like specified.
•
Check if Digital Input Brake Monitor 1 works correctly.
•
Check in Monitor Parameter
U1-10
if the input status changes.
Brake Monitor 2
•
Check if Motor Brake 2 operates correctly.
•
Check status of Motor Switch in Brake 2.
•
Check if the logic changes like specified.
•
Check if Digital Input Brake Monitor 2 works correctly.
•
Check in Monitor Parameter
U1-10
if the input status changes.
3
DI-A3 Option Multi-Functional Support
The DI-A3 option can be used to increase the number of digital inputs. To use this function, set parameter
F3-01
= 8 [DIA3 Option Input Selection = Multi-Functional]
. All standard functions can be assigned to the option
terminals D0 to D7 by using parameters
F3-04 to F3-11 [Terminal Dx Function Selection]
. If faults and alarms are
set to terminals D0 to D7, the display messages
„
OEF0
“
to
„
OEF7
“
[DI-A3 Ext Faultx]
will be shown. If no DI-A3
option card is installed, parameters
F3-04
to
F3-11
are not displayed. Parameters
F3-04
to
F3-11
are displayed
only when
F3-01 = 8
.
Summary of Contents for L1000A CIMR-LC F Series
Page 1: ...AC Drive L1000A For Lift Applications Technical Manual Addendum Type CIMR LCxFxxxxxxx 913x Web...
Page 98: ...15 Appendix 98 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Page 99: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 99 EN...
Page 100: ...15 Appendix 100 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Page 101: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 101 EN...
Page 102: ...15 Appendix 102 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...