Power-On dv/dt Threshold Tuning
When you set
L8-79 ≥ 100%
, the drive determines the value for
L8-70 [dv/dt Threshold]
during the first start after
power-on. The drive will save the value after the travel has ended. During this first start, the dv/dt method Input
Phase Loss Detection is disabled.
When you change
L8-79 [dv/dt Tuning Factor]
and confirm with Enter, the drive will determine the new value for
L8-70
during the next travel. The drive will save the value after the travel has ended.
The maximum dv/dt value during
S1-06 [Brake Release Delay Time]
is determined and saved. The drive
calculates the new dv/dt value as
S1-06 × L8-79
. This value is only stored when it differs ±50 V/s from the
existing setting of
L8-70
. When you set
L8-79 = 99%
, this tuning function is disabled, and L8-70 will not be
modified.
◆
Input Phase Loss Detection Method Selection
Use
L8-05 [Inp Ph Loss Det]
to activate the Input Phase Loss Detection function.
Parameter
(Hex.)
Operator Display
Description
Value Range
Default Value
L8-05
(04B1)
Inp Ph Loss Det
Input Phase Loss Detection Method
Enables or disables the input phase loss detection.
0 : Disabled
Lift controller decides the direction with S1/S2
2 : Enabled during operation
6 : St dv/dt
dv/dt @Start and Standard detection during RUN
0, 2, 6
2
◆
Further Modifications
■
Output Phase Loss Detection (OPLD)
OPLD During RUN :
The output phase loss detection function is modified to ensure that no false detections occur during RUN when
the lift car is balanced.
OPLD at Start :
Parameter
L8-81
sets the injection current for PM motors in % dependent on the selected motor rated current. The
threshold value for the phase loss detection is calculated and set to half of
|IU| = |IV|
value. If one of the phase
currents falls below this threshold for more than 100 ms,
LF
fault is triggered.
Figure 10.3 Output Phase Loss Detection Parameters and Timing During Injection
Summary of Contents for L1000A CIMR-LC F Series
Page 1: ...AC Drive L1000A For Lift Applications Technical Manual Addendum Type CIMR LCxFxxxxxxx 913x Web...
Page 98: ...15 Appendix 98 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Page 99: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 99 EN...
Page 100: ...15 Appendix 100 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Page 101: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 101 EN...
Page 102: ...15 Appendix 102 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...