Related Parameters and Monitors
■
Added Parameters
Parameter
(Hex.)
Operator Display
Description
Value Range
Default Value
L8-05
(04B1)
Inp Ph Loss Det
Input Phase Loss Detection Method
Enables or disables the input phase loss detection.
0 : Disabled
Lift controller decides the direction with S1/S2
2 : Enabled during operation
6 : St dv/dt
dv/dt @Start and Standard detection during RUN
0, 2, 6
2
L8-65
(067B)
PF Min Current
PF Detection Minimum Current Level
PF detection minimum current level; % of drive rated current. Used for both,
standard method and dv/dt method (only during run, not evaluated for dv/dt
detection method at start)
0.0 ... 100.0 %
10.0 %
L8-70
(066F)
Pf dv/dt Level
PF Detection Level
Sets the DC bus dv/dt threshold value.
0 ... 10,000 V/s
2,500 V/s
L8-79
(067E)
dv/dt TuneFactor
dV/dt tuning factor
Factor applied to the dv/dt value(s) which have been determined during tuning.
The result is stored to the parameter(s) if tuning was completed successfully.
100 ... 200 %
105 %
L8-81
(067F)
OutPhLs PMInjCur
Output Phase Loss PM Injection Current
Injection current for PM motor to detect output phase loss before the brake
opens.
0 ... 50.0 %
5 %
■
Added Monitors
Monitor
(Hex.)
Operator Display
Description
Analog Output
Scaling (H4-xx
selection)
Unit
U4-62
(085B)
PF dVdt ErrCount
PF detection error counter
Shows a percentage value less than 100%. If the value is different to zero,
there have been dv/dt threshold exceeding events. Upon reaching 100%, PF
fault is triggered and the counter is reset to 0%.
Note:
Only applies for dv/dt Input Phase Loss detection method.
-
ms
U4-64
(0859)
PF Max dVdtValue
PF detection maximum dV/dt value
Shows the maximum dv/dt value from the previous (or the current, while
running) travel. The value is reset at start and only updated while the drive is
running. When powering on (no previous travel), zero is shown.
The value is shown as absolute maximum dv/dt value (the internal value is
negative). The unit of this value is V/s but not shown in the operator.
Note:
Only applies for dv/dt Input Phase Loss detection method.
-
ms
U4-65
(085A)
PF dVdtValue
PF detection actual dV/dt value
Shows the current dv/dt value with sign. The value unit is V/s but not shown in
the operator.
Note:
Only applies for dv/dt Input Phase Loss detection method.
-
-
11
Direct Landing 2
◆
Overview
When you activate Direct Landing, the drive decelerates within a fixed distance to the floor level while it does a
positioning operation. You can define the distance to the floor, and also the frequency reference when Direct
Landing is activated.
EN
Summary of Contents for L1000A CIMR-LC F Series
Page 1: ...AC Drive L1000A For Lift Applications Technical Manual Addendum Type CIMR LCxFxxxxxxx 913x Web...
Page 98: ...15 Appendix 98 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Page 99: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 99 EN...
Page 100: ...15 Appendix 100 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Page 101: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 101 EN...
Page 102: ...15 Appendix 102 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...