38
YASKAWA
TOEPC710616134G AC Drive L1000A Technical Manual Addendum
1. The Speed Mode "Inspection [bit G4]" (VI) is transmitted before the travel starts.
2. The travel starts with activation of stop switch bit B2.
3. During the time the stop switch bit B2 is still activated, the drive continues to travel at crawl speed (V0).
4. Releasing the inspection button generally opens the safety circuit. That is why an electrical stop is not
possible. When the inspection function is deactivated, the lift controller must switch off drive controller
enable bit B0.
5. When during leveling speed a stop command is received, the drive should use
C1-02 [Ramp to Stop]
as for a
normal crawl travel.
Figure 6.5 Inspection Travel with V0 and Stopping with Idle Command
Summary of Contents for L1000A CIMR-LC F Series
Page 1: ...AC Drive L1000A For Lift Applications Technical Manual Addendum Type CIMR LCxFxxxxxxx 913x Web...
Page 98: ...15 Appendix 98 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Page 99: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 99 EN...
Page 100: ...15 Appendix 100 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Page 101: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 101 EN...
Page 102: ...15 Appendix 102 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...