Parameter
Operator Display
Description
Value Range
Default Value
S4-01 to S4-04,
S4-06 to S4-15
Rescue Operation
Rescue Operation Parameters
H5-13 ≥ 4: [not available]
S5-01 to S5-13
Short Floor Operation
Short Floor Operation Selection
H5-13 ≥ 4: [not available]
*1
Values not in parentheses apply when
o1-12 = 0
. Values in parentheses apply when
o1-12 = 1
.
*2
Applicable when
H5-13 = 4 [DCP4]
.
*3
Applicable when
H5-13 = 5 [CANopen-Lift]
(Profile Position Mode).
■
Modified Standard Monitors
Only modified parameters are listed in this table. If parameter H5-13 = 3 or 4 or 5, the following changes apply:
Monitor
Operator Display
Description
Analog Output
Scaling
Unit
U4-18
Reference Source
Displays the source for the speed reference as XY-nn.
X: Indicates which reference is used
1 : Reference 1 (b1-01)
Y-nn: Indicates the reference source
0-01 : Digital Operator
1-01 : Analog (Terminal A1)
1-02 : Analog (Terminal A2)
3-01 : MEMOBUS/Modbus communications
4-01 : Communication Option Card
5-00 : CANopen-Lift
6-00 : DCP
-
Hex
U4-21
Run Cmd Source
Displays the source for the Up/Down command as XY-nn.
X: Indicates which Up/Down command source is used
1 : Reference 1 (b1-02)
Y: Input power supply data
0 : Digital Operator
1 : External Terminals
3 : MEMOBUS/Modbus communications
4 : Communication Option Card
5 : CANopen-Lift
6 : DCP
nn: Up/Down command limit status data
00 : No limit status
01 : Up/Down command was left on when stopped in PRG mode
02 : Up/Down command was left on when switching from LOCAL to
REMOTE operation
03 : Waiting for soft charge bypass contactor after power up (Uv or
Uv1 flashes after 10 s)
04 : Waiting for “Up/Down Command Prohibited” time period to
end
05 : Emergency Stop (multi-function input, operator)
07 : During baseblock while coast to stop with timer
08 : Speed reference is below minimal reference during baseblock
09 : Wairing for Enter command
-
Hex
U4-42 to U4-44
Direct Landing
H5-13 ≥ 4: [not available]
■
Added Standard Monitors
Monitor
Operator Display
Description
Analog Output
Scaling (H4-xx
selection)
Unit
U4-50
Rem Distance
Remaining Distance
Shows the remaining distance until the commanded distance is reached (value
originating from lift controller, contains distance prolongations)
10 V:
65.535 m
(2580.12 in)
0.001 m
(0.01 in)
U4-51
Braking Distance
Braking Distance
Shows the braking distance for a currently driven speed (matches the
remaining distance at the time of deceleration)
10 V:
65.535 m
(2580.1 in)
0.001 m
(0.1 in)
U4-52
Int Dist Cmd
Internal Distance Command
Shows the total commanded distance including prolongations (calculated from
remaining distance)
10 V:
100.00 m
(3937.0 in)
0.01 m
(0.1 in)
U4-55
Shft Ctrl Input
Shaft Controller Input
Shows the difference between remaining distance based on shaft PG and motor
PG
-
0.001 m
(0.01 in)
U4-56
Shft Ctrl Output
Shaft Controller Output
Shows the shaft controller output correction value per scan, added to the
absolute position value based on motor PG
-
0.001 m
(0.01 in)
EN
Summary of Contents for L1000A CIMR-LC F Series
Page 1: ...AC Drive L1000A For Lift Applications Technical Manual Addendum Type CIMR LCxFxxxxxxx 913x Web...
Page 98: ...15 Appendix 98 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Page 99: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 99 EN...
Page 100: ...15 Appendix 100 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Page 101: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 101 EN...
Page 102: ...15 Appendix 102 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...