324
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
Set
F2-01 = 0
to increase the precision of A/D conversion when you use the functions for terminals A1 to A3 on the
drive as they are. You can input the MFAI signal from terminals V1 through V3 for AI-A3. The functions for
terminals A1, A2, and A3 on the drive are sent to terminals V1, V2, and V3 for AI-A3. Use gain and bias adjustment
when you input current to set signals to have negative numbers.
Note:
•
Set
b1-01 = 1 [Frequency Reference Selection 1 = Analog Input]
to set inputs individually.
•
If
F2-01 = 0
and
b1-01 = 3 [Option PCB]
, the drive will detect
oPE05 [Run Cmd/Freq Ref Source Sel Err]
.
shows the individual input of analog inputs.
H3-xx parameters
set the function to input the analog
reference received from the AI-A3 card and to adjust the gain and bias of these signals.
Figure 2.74 Analog Input Reference Individual Input Block Diagram
1 : 3 Channels Added Together
Set
b1-01 = 3 [Option PCB]
to set addition input.
You can input the frequency reference directly. The sum value when you add the input from terminals V1 to V3
becomes the frequency reference.
Set
F2-01 = 1
to use the AI-A3 card as addition input.
shows addition input. Use
F2-02 [Analog Input Option Card Gain]
and
F2-03 [Analog Input Option Card
Bias]
to adjust the analog reference gain and bias for addition input.
Figure 2.75 Analog Input Reference Addition Input Block Diagram
Use F2-02 and F2-03 to Adjust the Input Status
When the bias set in
F2-03
is 0%, the gain in
F2-02
and the addition input value set the ratio (%) of the maximum
output frequency output as the frequency reference.
Note:
A voltage input of 10 V or a current input of 20 mA is the 100% value for each channel.
The bias set in
F2-03
sets the ratio (%) of the maximum output frequency output as the frequency reference when the
addition input value is 0%.
Note:
A voltage input of 0 V or a current input of 4 mA is the 0% value for each channel.