2.2 A: Initialization Parameters
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
185
Figure 2.1 Frequency Detection 2
Sequence Circuit Configuration
Use these conditions to set the circuit for the open/close sequence of the holding brake:
•
Set the sequence-side operation conditions to activate terminal M1-M2 and open the holding brake.
•
Set the sequence to close the holding brake in an emergency if the drive detects a fault.
•
Set the sequence to open the holding brake when you enter an increase or decrease command.
Figure 2.2 Sequence Circuit Configuration Diagram
*1
L4-07 = 0 [Speed Agree Detection Selection = No Detection during Baseblock]
or During Frequency Output
Time Chart
shows the open/close sequence of the holding brake.
Figure 2.3 Holding Brake Open and Close Sequence Time Chart (V/f, CL-V/f, OLV)
*1
Start braking from the higher set frequency between
b2-01 [DC Injection/Zero SpeedThreshold]
or
E1-09
[Minimum Output Frequency]
.