1.21 Defaults by Drive Model and Duty Rating ND/HD
146
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
No.
Name
Unit
Default
-
Drive Model
-
4075
4089
4103
4140
C6-01
Normal /
Heavy Duty
Selection
-
HD
ND
HD
ND
HD
ND
HD
ND
0
1
0
1
0
1
0
1
o2-04
Drive Model
(KVA)
Selection
Hex.
A1
A2
A3
A4
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP (kW)
40
(30)
50
(37)
50
(37)
60
(45)
60
(45)
75
(55)
75
(55)
100
(75)
L8-09
Output Ground
Fault
Detection
-
1
1
1
1
1
1
1
1
L8-38
Carrier
Frequency
Reduction
-
2
2
2
2
2
2
2
2
n1-01
Hunting
Prevention
Selection
-
2
2
2
2
2
2
2
2
n1-03
Hunting
Prevention
Time Constant
ms
10
10
10
10
10
10
30
30
n5-02
Motor Inertia
Acceleration
Time
s
0.323
0.32
0.32
0.387
0.387
0.317
0.317
0.533
*1
Parameters within parentheses are for motor 2.
No.
Name
Unit
Default
-
Drive Model
-
4168
4208
4250
4302
C6-01
Normal /
Heavy Duty
Selection
-
HD
ND
HD
ND
HD
ND
HD
ND
0
1
0
1
0
1
0
1
o2-04
Drive Model
(KVA)
Selection
Hex.
A5
A6
A7
A8
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP (kW)
100
(75)
125
(90)
125
(90)
150
(110)
150
(110)
175
(132)
175
(132)
200
(160)
b3-04
V/f Gain
during Speed
Search
%
60
60
60
60
60
60
60
60
b3-06
Speed
Estimation
Current Level
1
-
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
b3-08
Speed
Estimation
ACR P Gain
-
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
b3-26
Direction
Determination
Level
-
1000
1000
1000
1000
1000
1000
1000
1000
b8-03
Energy Saving
Filter Time
s
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
b8-04
Energy Saving
Coefficient
Value
-
46.2
38.91
38.91
36.23
36.23
32.79
32.79
30.13
C5-17
(C5-37)
Motor Inertia
kgm
2
0.90
1.10
1.10
1.90
1.90
2.10
2.10
3.30
C6-02
Carrier
Frequency
Selection
-
1
7
1
7
1
7
1
7
E2-01
(E4-01)
Motor Rated
Current (FLA)
A
130
156
156
190
190
223
223
270
E2-02
(E4-02)
Motor Rated
Slip
Hz
1.39
1.4
1.4
1.4
1.4
1.38
1.38
1.35