406
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
Drives have three analog input terminals, terminals A1, A2, and A3.
H3 parameters
select the functions set to these
analog input terminals and adjust signal levels.
shows the functions that you can set to analog input terminals. Use
H3-02, H3-06, and H3-10 [MFAI
Function Selection]
to set functions.
Table 2.64 MFAI Setting Values
Setting
Value
Function
Ref.
0
Frequency Reference
1
Frequency Gain
2
Auxiliary Frequency Reference 1
3
Auxiliary Frequency Reference 2
4
Output Voltage Bias
5
Accel/Decel Time Gain
6
DC Injection Braking Current
7
Torque Detection Level
8
Stall Prevent Level During Run
9
Output Frequency Lower Limit
B
PID Feedback
C
PID Setpoint
D
Frequency Bias
Setting
Value
Function
Ref.
E
Motor Temperature (PTC Input)
F
Not Used
10
Forward Torque Limit
11
Reverse Torque Limit
12
Regenerative Torque Limit
13
Torque Reference / Torque Limit
14
Torque Compensation
15
General Torque Limit
16
Differential PID Feedback
1F
Not Used
30
DWEZ Analog Input 1
31
DWEZ Analog Input 2
32
DWEZ Analog Input 3
Note:
All analog input scaling uses gain and bias for adjustment. Set the gain and bias values correctly.