TOEPYAIGA8002B GA800 Drive Programming
■
H3-16: Terminal A1 Offset
No.
(Hex.)
Name
Description
Default
(Range)
H3-16
(02F0)
Terminal A1 Offset
Sets the offset level for analog signals input to terminal A1. Usually it is not necessary to change this
setting.
0
(-500 - +500)
Adds the offset value for the analog input value. For voltage input, this parameter will set the offset when a signal of 0
V is input. For current input, this parameter will set the offset when a signal of
4 mA [H3-01= 2]
or
0 mA [H3-01 = 3]
is input.
■
H3-17: Terminal A2 Offset
No.
(Hex.)
Name
Description
Default
(Range)
H3-17
(02F1)
Terminal A2 Offset
Sets the offset level for analog signals input to terminal A2. Usually it is not necessary to change this
setting.
0
(-500 - +500)
Adds the offset value for the analog input value. For voltage input, this parameter will set the offset when a signal of 0
V is input. For current input, this parameter will set the offset when a signal of
4 mA [H3-09 = 2]
or
0 mA [H3-09 =
3]
is input.
■
H3-18: Terminal A3 Offset
No.
(Hex.)
Name
Description
Default
(Range)
H3-18
(02F2)
Terminal A3 Offset
Sets the offset level for analog signals input to terminal A3. Usually it is not necessary to change this
setting.
0
(-500 - +500)
Adds the offset value for the analog input value. For voltage input, this parameter will set the offset when a signal of 0
V is input. For current input, this parameter will set the offset when a signal of
4 mA [H3-05 = 2]
or
0 mA [H3-05 =
3]
is input.
■
H3-40: Mbus Reg 15C1h Input Function
No.
(Hex.)
Name
Description
Default
(Range)
H3-40
(0B5C)
Mbus Reg 15C1h Input
Function
Sets the MEMOBUS AI1 function.
F
(4 - 2F)
You can use the MFAI function from MEMOBUS/Modbus communications. Use this parameter to set the function.
Sets the input for the function in MEMOBUS/Modbus register 15C1.
Refer to H3-xx
“
MFAI Setting Values
”
for the setting values.
■
H3-41: Mbus Reg 15C2h Input Function
No.
(Hex.)
Name
Description
Default
(Range)
H3-41
(0B5F)
Mbus Reg 15C2h Input
Function
Sets the MEMOBUS AI2 function.
F
(4 - 2F)
You can use the MFAI function from MEMOBUS/Modbus communications. Use this parameter to set the function.
Sets the input for the function in MEMOBUS/Modbus register 15C2.
Refer to H3-xx
“
MFAI Setting Values
”
for the setting values.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV