1.20 Parameters Changed by E1-03 [V/f Pattern Selection]
132
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
Table 1.3 Parameters Changed by E1-03 (2257 to 2415 and 4140 to 4720)
No.
Unit
Setting Value
Control Method (A1-02 Setting)
E1-
03
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
OLV
(2)
CLV
(3)
OLV/
PM
(5)
AOL-
V/PM
(6)
CLV/
PM
(7)
E1-04
Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120.0
180.0
60.0
60.0
60.0
E1-05
V
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
E1-06
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
E1-07
Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
3.0
0.0
-
-
-
E1-08
V
13.8
13.8
13.8
13.8
40.3
57.5
40.3
57.5
17.3
23.0
17.3
23.0
13.8
13.8
13.8
13.8
12.7
0.0
-
-
-
E1-09
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
1.5
0.5
0.0
0.0
E1-10
V
6.9
6.9
6.9
6.9
5.8
6.9
5.8
6.9
8.1
10.4
8.1
12.7
6.9
6.9
6.9
6.9
2.3
0.0
-
-
-
*1
These values are the default settings for
E1-04 to E1-10
and
E3-04 to E3-10 [V/f Pattern for Motor 2]
. These settings are the same as
those for the V/f pattern when
E1-03 = 1 [Const Trq, 60Hz base, 60Hz max]
.
*2
The default setting varies depending on the setting of
E5-01 [PM Motor Code Selection]
.
*3
This is the value for 200 V class drives. Double the value for 400 V class drives.