Order no.
314-6CF23
Input characteristic curve
IEC 61131-2, type 1
Initial data size
34 Byte
Technical data digital outputs
Number of outputs
8
Cable length, shielded
1000 m
Cable length, unshielded
600 m
Rated load voltage
DC 24 V
Reverse polarity protection of rated load voltage
-
Current consumption from load voltage L+ (without load)
30 mA
Total current per group, horizontal configuration, 40°C
4 A
Total current per group, horizontal configuration, 60°C
3 A
Total current per group, vertical configuration
3 A
Output voltage signal "1" at min. current
L+ (-0.8 V)
Output voltage signal "1" at max. current
L+ (-0.8 V)
Output current at signal "1", rated value
0.5 A
Signal logic output
Sinking output
Output current, permitted range to 40°C
5 mA to 0.6 A
Output current, permitted range to 60°C
5 mA to 0.6 A
Output current at signal "0" max. (residual current)
100 µA
Output delay of "0" to "1"
100 µs
Output delay of "1" to "0"
100 µs
Minimum load current
-
Lamp load
5 W
Parallel switching of outputs for redundant control of a load possible
Parallel switching of outputs for increased power
not possible
Actuation of digital input
ü
Switching frequency with resistive load
max. 2.5 kHz
Switching frequency with inductive load
max. 0.5 Hz
Switching frequency on lamp load
max. 2.5 kHz
Internal limitation of inductive shut-off voltage
L+ (-52 V)
Short-circuit protection of output
yes, electronic
Trigger level
1 A
Number of operating cycle of relay outputs
-
Switching capacity of contacts
-
Output data size
18 Byte
Technical data analog inputs
VIPA System 300S
+
Hardware description
Technical data
HB140 | CPU | 314-6CF23 | en | 19-01
39