The initialization via PLC functions takes place with the following proceeding:
Determine the current Ethernet (MAC) address of your Ethernet PG/OP channel.
This always may be found as 1. address under the front flap of the CPU on a sticker
on the left side.
You get valid IP address parameters from your system administrator. The assignment of
the IP address data happens online in the Siemens SIMATIC Manager starting with ver-
sion V5.5 + SP1 with the following proceeding:
1.
Start the Siemens SIMATIC Manager and set via
‘Options
è
Set PG/PC interface’
the access path to
‘TCP/IP -> Network card ....’
.
2.
Open with
‘PLC
è
Edit Ethernet Node n’
the dialog window with the same name.
3.
To get the stations and their MAC address, use the [Browse] button or type in the
MAC Address. The Mac address may be found at the 1. label beneath the front flap
of the CPU.
4.
Choose if necessary the known MAC address of the list of found stations.
5.
Either type in the IP configuration like IP address, subnet mask and gateway.
6.
Confirm with [Assign IP configuration].
ð
Direct after the assignment the Ethernet PG/OP channel may be reached online
by these address data. The value remains as long as it is reassigned, it is over-
written by a hardware configuration or an factory reset is executed.
1.
Open the Siemens hardware configurator und configure the Siemens CPU 317-2DP
(6ES7 317-2AK14-0AB0 V3.3).
2.
Configure the modules at the standard bus.
3.
For the Ethernet PG/OP channel you have to configure a Siemens CP 343-1
(SIMATIC 300 \ CP 300 \ Industrial Ethernet \CP 343-1 \ 6GK7 343-1EX11 0XE0)
always below the really plugged modules.
4.
Open the property window via double-click on the CP 343-1EX11 and enter for the
CP at
‘Properties’
the IP address data, which you have assigned before.
5.
Assign the CP to a
‘Subnet’
. Without assignment the IP address data are not used!
6.
Transfer your project.
"Initialization" via PLC
functions
Assign IP address param-
eters
Take IP address parame-
ters in project
VIPA System 300S
+
Deployment CPU 314-6CF23
Hardware configuration - Ethernet PG/OP channel
HB140 | CPU | 314-6CF23 | en | 19-01