Order no.
314-6CF23
Destruction limit against external applied voltage
max. 15V
Current outputs
ü
Max. in load resistance (current range)
500 Ω
Max. inductive load (current range)
10 mH
Typ. open circuit voltage current output
16 V
Output current ranges
-20 mA ... +20 mA
0 mA ... +20 mA
+4 mA ... +20 mA
Operational limit of current ranges
+/-0.4%
Radical error limit current ranges with SFU
+/-0.3%
Destruction limit against external applied voltage
max. 15V
Settling time for ohmic load
0.2 ms
Settling time for capacitive load
0.5 ms
Settling time for inductive load
0.75 ms
Resolution in bit
12
Conversion time
1 ms
Substitute value can be applied
yes
Output data size
4 Byte
Technical data counters
Number of counters
4
Counter width
32 Bit
Maximum input frequency
100 kHz
Maximum count frequency
100 kHz
Mode incremental encoder
ü
Mode pulse / direction
ü
Mode pulse
ü
Mode frequency counter
-
Mode period measurement
-
Gate input available
ü
Latch input available
ü
Reset input available
ü
Counter output available
ü
Load and working memory
Load memory, integrated
2 MB
Load memory, maximum
2 MB
Work memory, integrated
512 KB
VIPA System 300S
+
Hardware description
Technical data
HB140 | CPU | 314-6CF23 | en | 19-01