Input area (channel 4)
No.
Function
Input area
82h
Pt100 in 2wire mode
-240...1000°C
1000°C = End overdrive region (10000)
-200...+850°C = Nominal range (-2000 ... 8500)
-240°C = End underdrive region (-2400)
two’s complement
85h
Pt100 in 2wire mode
-240...600°C
600°C = End overdrive region (6000)
-200...+500°C = Nominal range (-2000 ... 5000)
-240°C = End underdrive region (-2400)
two’s complement
83h
NI100 in 2wire mode
-105...295°C
295°C = End overdrive region (2950)
-50...+250°C = Nominal range (-500 ... 2500)
-105°C = End underdrive region (-1050)
two’s complement
86h
NI1000 in 2wire mode
-105...270°C
270°C = End overdrive region (2700)
-50...+250°C = Nominal range (-500 ... 2500)
-105°C = End underdrive region (-1050)
two’s complement
46h
Resistance measurement
600
Ω
2wire
0...705.5
Ω
705.5
Ω
= End overdrive region (32511)
0...600
Ω
= Nominal range (0 ... 27648)
no underdrive region available
00h
Channel not active (turned off)
Output area (channel 5, channel 6)
No.
Function
Output area
19h
Voltage ±10V
S7 format from Siemens
±11.76V
11.76V= End overdrive region (32511)
-10...10mA = Nominal range (-27648 ... 27648)
-11.76V = End underdrive region (-32512)
two’s complement
18h
Voltage 0...10V
S7 format from Siemens
0...11.76V
11.76V = End overdrive region (32511)
0...10V = Nominal range (0 ... 27648)
no underdrive region available
VIPA System 300S
+
Deployment I/O periphery
Analog part - Parametrization
HB140 | CPU | 314-6CF23 | en | 19-01
104