Address
Access
Assignment
+10
Word
Analog input CH3
+12
Word
Analog input CH4
Used area
Address
Access
Assignment
+4
Word
Analog output CH0
+6
Word
Analog output CH1
The analog values are represented in two’s complement format. Depending on the para-
metrized transformation speed the lowest value bits of the measuring value are irrelevant.
With increasing sampling rate, the resolution decreases. The following table lists the res-
olution in dependence of the sampling rate. The lowest value irrelevant bits of the output
value are marked with "X".
Resolution
Analog value
High byte (byte 0)
Low byte (byte 1)
Bit number
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Significance
sign
2
14
2
13
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
15bit + sign
sign
Relevant output value (at 3.7 ... 30Hz)
14bit + sign
sign
Relevant output value (at 60Hz)
X
13bit + sign
sign
Relevant output value (at 120Hz)
X
X
11bit + sign
sign
Relevant output value (at 170Hz)
X
X
X
X
9bit + sign
sign
Relevant output value (at 200Hz)
X
X
X
X
X
X
For the sign bit is valid:
n
Bit 15 = "0":
à
positive value
n
Bit 15 = "1":
à
negative value
As soon as a measuring value exceeds overrange respectively unterrange, the following
value is returned:
n
Measured value > overrange
–
32767 (7FFFh)
n
Measured value < unterrange
–
-32768 (8000h)
At wire break, parametrization error or deactivated analog part the measuring value
32767 (7FFFh) is returned.
With this record set 9Eh you may de-activate the digital respectively analog part. Please
regard that in spite of the de-activation of the digital res. analog part, the process image
for both components remains reserved. The record set has the following structure:
Numeric notation in Sie-
mens S7 format
Algebraic sign bit (sign)
Behavior at errors
De-activate analog part
VIPA System 300S
+
Deployment I/O periphery
Analog part
HB140 | CPU | 314-6CF23 | en | 19-01