Thus, the VIPA components can be displayed, you have to deactivate the
"Filter" of the hardware catalog.
The embedding of the CPU 314-6CF23 happens by means of a virtual PROFIBUS
master system with the following approach:
1.
Start the Siemens TIA Portal.
2.
Configure in the Device configuration the according Siemens CPU.
3.
Configure your System 300 modules.
4.
Configure your Ethernet PG/OP channel always as last module after the really
plugged modules.
5.
Configure always as last module a Siemens DP master CP 342-5 (342-5DA02
V5.0). Connect and parameterize it at operation mode "DP-Master".
Device overview
Module
...
Slot
...
Type
...
PLC...
2
CPU ...
...
...
...
3
DI...
4
DI...
DO...
5
DO...
DIO...
6
DIO...
AI...
7
AI...
AO...
8
AO...
CP 343-1
9
CP 343-1
CP 342-5
10
CP 342-5
Proceeding
VIPA System 300S
+
Configuration with TIA Portal
TIA Portal - Setting VIPA specific CPU parameters
HB140 | CPU | 314-6CF23 | en | 19-01