Measuring range
Current
(I)
Decimal
(D)
Hex
Range
Conversion
4 ... 20mA
22.81mA
32511
7EFFh
overrange
20mA
27648
6C00h
nominal range
12mA
13824
3600h
4mA
0
0000h
1.19mA
-4864
ED00h
underrange
Measuring range
Current
(I)
Decimal
(D)
Hex
Range
Conversion
±20mA
23.52mA
32511
7EFFh
overrange
20mA
27648
6C00h
nominal range
10mA
13824
3600h
0mA
0
0000h
-10mA
-13824
CA00h
-20mA
-27648
9400h
-23.52mA
-32512
8100h
underrange
6.5 Analog part - Parametrization
18Byte of parameter data are available for the configuration. By using the record set B4h
of the SFC 55 "WR_PARM" you may alter the parametrization in the module during run-
time. The time needed until the new parametrization is valid can last up to 50ms. During
this time, the measuring value output is 7FFFFh. The following table shows the structure
of the parameter data:
Parameter data
VIPA System 300S
+
Deployment I/O periphery
Analog part - Parametrization
HB140 | CPU | 314-6CF23 | en | 19-01
100