Byte
Record set
Description
4
9Dh
C3: Count value that is transferred to counter by setting bit 5 in the output status word
2
9Eh
Activate respectively de-activate analog/digital part
Except of the parameter in record set 0, you may transfer the other parameters during
runtime by using the SFC 55, 56, 57 and 58 to the digital part. For this you have to
transfer the wanted parameters via record set to the counter by using the according SFC
in the user application.
Byte
Bit 7...0
0...3
Counter mode C0
4...7
Counter mode C1
8...11
Counter mode C2
12...15
Counter mode C3
n
Via the record set 0 you may preset a counter mode for every counter as double
word.
n
Record set 0 may not be transferred during runtime.
Record set 0 -
Counter mode
VIPA System 300S
+
Deployment I/O periphery
Counter - Parametrization
HB140 | CPU | 314-6CF23 | en | 19-01
115