H5-04
Stopping Method After
Communication Error
Selects the stopping method when a communication time-out
fault (CE) is detected.
0: Ramp to stop
1: Coast to stop
2: Fast-stop
3: Alarm only
0 to 3
3
A A A
428
H5-05
Communication Fault
Detection Selection
Enables or disables the communications time-out fault (CE)
detection.
0: Disabled
1: Enabled - If communication is lost for more than two
seconds, a CE fault will occur.
0, 1
1
A A A
429
H5-06
Drive Transmit Wait Time
Set the wait time between receiving and sending data.
5 to 65
5 ms A A A
42A
H5-07
RTS Control Selection
Selects "request to send" (RTS) control:
0: Disabled - RTS is always on.
1: Enabled - RTS turns on only when sending.
0, 1
1
A A A
42B
H5-09
CE Detection Time
Sets the time required to detect a communications error.
Adjustment may be need when networking several drives.
0.0 to 10.0
s
2.0 s A A A
435
H5-10
Unit Selection for
MEMOBUS/Modbus
Register 0025H
Selects the units used for MEMOBUS/Modbus register
0025H (Output Voltage Reference Monitor).
0: 0.1 V units
1: 1 V units
0, 1
0
A A A
436
H5-11
Communications ENTER
Function Selection
Select the function for the enter command that saves
parameter data to the drive.
0: Parameter changes are activated when ENTER command
is entered.
1: Parameter changes are activated immediately without
ENTER command (compatible with Varispeed VS606-V7).
0, 1
1
A A A
43C
H5-12
Run Command Method
Selection
0: FWD/STOP, REV/STOP Method
1: RUN/STOP, FWD/REV Method
0, 1
0
A A A
43D
H6: Pulse Train Input/Output
Use H6 parameters to configure Pulse Train I/O operation.
H6-01
Pulse Train Input Terminal
RP Function Selection
Selects pulse train input function.
0: Frequency reference
1: PID feedback value
2: PID setpoint value
3: V/f Control with Simple PG Feedback (can be set only when
using motor 1 in V/f Control)
0 to 3
0
A A A
42C
H6-02
<2>
Pulse Train Input Scaling
Sets the terminal RP input signal frequency that is equal to
100% of the value selected in H6-01.
<4>
1440
Hz
A A A
42D
H6-03
<2>
Pulse Train Input Gain
Sets the level of the value selected in H6-01 when a frequency
with the value set in H6-02 is input.
0.0 to
1000.0
100.0
%
A A A
42E
H6-04
<2>
Pulse Train Input Bias
Sets the level of the value selected in H6-01 when 0 Hz is
input.
-100.0 to
+100.0
0.0% A A A
42F
H6-05
<2>
Pulse Train Input Filter
Time
Sets the pulse train input filter time constant.
0.00 to
2.00
0.10 s A A A
430
H6-06
<2>
Pulse Train Monitor Terminal
MP Selection
Select the pulse train monitor output function (value of the
o
-
oo
part of U
o
-
oo
).
Refer to U: Monitors on page 399
for the list of U monitors.
Example: To select U5-01, set “501. ”When not using this
parameter or when using in the through mode, set “000”.
<5>
000, 031,
101, 102,
105, 116,
501, 502;
801 to 809
102
A A A
431
H6-07
<2>
Pulse Train Monitor Scaling
Sets the terminal MP output signal frequency when the
monitor value is 100%. Set H6-06 to 102 and H6-07 to 0 to
make the pulse train monitor output equal to the output
frequency.
0 to 32000 1440
Hz
A A A
432
<1> The availability of certain functions depends on the control method used.
<2> Parameter can be changed during Run.
<3> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
<4> Default setting is determined by drive software version.
PRG: 1016 and later: 100 to 32000 Hz
B.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
383