Register No.
Contents
00D0H
CPF Contents 1
bit 0 to 1
Reserved
bit 2
A/D Conversion Error (CPF02)
bit 3
PWM Data Fault (CPF03)
bit 4 to 5
Reserved
bit 6
Drive specification mismatch during Terminal Board or Control Board replacement (CPF06)
bit 7
Terminal Board Communications Fault (CPF07)
bit 8
EEPROM Serial Communications Fault (CPF08)
bit 9 to A
Reserved
bit B
RAM Fault (CPF11)
bit C
FLASH Memory Fault (CPF12)
bit D
Watchdog Circuit Exception (CPF13)
bit E
Control Circuit Fault (CPF14)
bit F
Reserved
00D1H
CPF Contents 2
bit 0
Clock Fault (CPF16)
bit 1
Timing Fault (CPF17)
bit 2
Control Circuit Fault (CPF18)
bit 3
Control Circuit Fault (CPF19)
bit 4
Hardware fault at power up (CPF20)
bit 5
Hardware fault at communication start up (CPF21)
bit 6
A/D Conversion Fault (CPF22)
bit 7
PWM Feedback Fault (CPF23)
bit 8
Drive capacity signal fault (CPF24)
bit 9
Terminal board is not properly connected (CPF25)
bit A to F
Reserved
00D8H
Option Card Fault Contents
bit 0
Option Compatibility Error (oFA00)
bit 1
Option not properly connected (oFA01)
bit 3
Option Self-diagnostics Error (oFA03)
bit 4
Option Flash Write Mode Error (oFA04)
bit 5 to F
Reserved
00FBH
Output Current
<2>
<1> Units are determined by parameter o1-03.
<2> Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units.
2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units.
<3> The communication error log is stored until the fault is reset.
<4> Depending on the motor used the correct motor pole number must be set to parameter E2-04, E4-04 or E5-05.
<5> Available in drive software versions PRG: 1011 and later.
C.10 MEMOBUS/Modbus Data Table
456
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual