No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M
C6-03
Carrier Frequency Upper
Limit
Note:
Set C6-02 to F before setting C6-03.
Open Loop Vector: C6-03 defines the fixed carrier
frequency if C6-02 = F.
V/f Control: C6-03 and C6-04 set upper and lower limits
for the carrier frequency.
carrier frequency
E1-04
max output
frequency
output frequency
× (C6-05) × K
output
frequency
C6-03
C6-04
The coefficient K depends on C6-03:
C6-03 ≥ 10.0 kHz: K = 3
10.0 kHz > C6-03 ≥ 5.0 kHz: K = 2
5.0 kHz > C6-03: K = 1
When C6-05 ≤ 6, C6-04 is disabled (makes the carrier
frequency C6-03 value).
1.0 to 15.0
<9>
A A A
225
C6-04
Carrier Frequency Lower
Limit
1.0 to 15.0
<9>
A
-
-
226
C6-05
Carrier Frequency
Proportional Gain
Sets the relationship of output frequency to carrier
frequency when C6-02 = F.
00 to 99
<9>
A
-
-
227
<1> Parameter can be changed during run.
<2> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range
becomes 0.00 to 600.00 seconds.
<3> Available in drive software versions PRG: 1020 and later.
<4> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control.
<5> Parameter cannot be changed during run when parameter A1-02 = 5-PM OLV Control.
<6> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 2-OLV control.
<7> Setting range is determined by the drive software version.
PRG: 1020 and later: 1 to B; F
PRG: 1018 and earlier: 1 to A; F
<8> Default setting value is dependent on parameters o2-04, Drive Model Selection, A1-02, Control Method Selection and C6-01, Drive Duty Selection.
<9> Default setting value is dependent on parameter C6-02, Carrier Frequency Selection.
<10> Available in drive software versions PRG: 1024 and later.
u
d: References
Reference parameters are used to set the various frequency reference values during operation.
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/
f
O
L
V
P
M
d1: Frequency Reference
Use d1 parameters to configure the drive frequency reference.
d1-01
<1>
Frequency Reference 1
Frequency reference.
Refer to b1-01: Frequency Reference
for instructions to use d1-01 as the main
frequency reference.
0.00 to
400.00 Hz
<2>
<3>
0.00
Hz
S
S
S
280
d1-02
<1>
Frequency Reference 2
Frequency reference when digital input "Multi-Step Speed
Reference 1" (H1-
oo
= 3) is on.
0.00
Hz
S
S
S
281
d1-03
<1>
Frequency Reference 3
Frequency reference when digital input "Multi-Step Speed
Reference 2” (H1-
oo
= 4) is on.
0.00 to
400.00 Hz
<2>
<3>
0.00
Hz
S
S
S
282
d1-04
<1>
Frequency Reference 4
Frequency reference when digital inputs "Multi-Step Speed
Reference 1, 2" (H1-
oo
= 3 and 4) are on.
0.00
Hz
S
S
S
283
d1-05
<1>
Frequency Reference 5
Frequency reference when digital input "Multi-Step Speed
Reference 3" (H1-
oo
= 5) is on.
0.00 to
400.00 Hz
<2>
<3>
0.00
Hz
A A A
284
d1-06
<1>
Frequency Reference 6
Frequency reference when digital inputs "Multi-Step Speed
Reference 1, 3 " (H1-
oo
= 3 and 5) are on.
0.00
Hz
A A A
285
B.2 Parameter Table
364