No.
Parameter Name
Default Setting
L8-07
Output Phase Loss Protection Selection
1: Triggered when a single phase is lost
L8-38
Carrier Frequency Reduction
1: Enabled below 6 Hz
L8-41
High Current Alarm Selection
1: Enabled (alarm output)
<1> Disable L8-05 for single-phase models.
Table 4.18 Preset 7: User Parameters (A2-01 to A2-16):
No.
Parameter Name
No.
Parameter Name
b1-01
Frequency Reference Selection 1
d1-03
Frequency Reference 3
C1-01
Acceleration Time 1
E2-01
Motor Rated Current
C1-02
Deceleration Time 1
H1-05
Multi-Function Digital Input Terminal S5 Function
C6-02
Carrier Frequency Selection
H1-06
Multi-Function Digital Input Terminal S6 Function
d1-01
Frequency Reference 1
H2-01
Terminals MA, MB, and MC Function Selection
d1-02
Frequency Reference 2
L1-01
Motor Overload Protection Selection
u
Setting 8: Conveyor Application 2
This setting is available in drive software versions PRG: 1020 and later.
Table 4.19 Conveyor 2: Parameters and Settings
No.
Parameter Name
Default Setting
A1-02
Control Method Selection
0: V/f Control
C1-01
Acceleration Time 1
3.0 s
C1-02
Deceleration Time 1
3.0 s
C6-01
Drive Duty Selection
0: Heavy Duty
L3-04
Stall Prevention Selection during Deceleration
0: Disabled
n3-13
Overexcitation Deceleration Gain
1.4
n3-21
High-Slip Suppression Current Level
150%
Table 4.20 Conveyor 2: User Parameters (A2-01 to A2-16):
No.
Parameter Name
No.
Parameter Name
A1-02
Control Method Selection
E2-01
Motor Rated Current
b1-01
Frequency Reference Selection 1
L3-04
Stall Prevention Selection during Deceleration
b1-02
Run Command Selection 1
n3-13
Overexcitation Deceleration Gain
C1-01
Acceleration Time 1
n3-21
High-Slip Suppression Current Level
C1-02
Deceleration Time 1
–
–
4.6 Application Selection
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
101
4
Start-Up Programming & Operation