Drive
Model
Terminal
Recomm.
Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening
Torque
N•m (lb.in.)
4A0031
R/L1, S/L2, T/L3
8
10 to 6
M5
3.6 to 4.0
(31.8 to 35.4)
U/T1, V/T2, W/T3
8
10 to 6
⊖
,
⊕
1,
⊕
2
–
10 to 6
B1, B2
–
14 to 10
2.7 to 3.0
(23.9 to 26.6)
6
<1>
10 to 6
M6
5.4 to 6.0
(47.8 to 53.1)
4A0038
R/L1, S/L2, T/L3
6
10 to 6
M5
3.6 to 4.0
(31.8 to 35.4)
U/T1, V/T2, W/T3
8
10 to 6
⊖
,
⊕
1,
⊕
2
–
10 to 6
B1, B2
–
10 to 8
2.7 to 3.0
(23.9 to 26.6)
6
10 to 6
M6
5.4 to 6.0
(47.8 to 53.1)
<1> When an EMC filter is installed, additional measures must be taken to comply with IEC/EN 61800-5-1.
Refer to EMC Filter Installation on page
Note:
Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum allowable
temperature of 75 °C 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed 30 °C.
Closed-Loop Crimp Terminal Recommendations
Yaskawa recommends crimp terminals made by JST and Tokyo DIP for the insulation cap.
matches the wire gauges and terminal screw sizes with Yaskawa-recommended crimp terminals, tools, and insulation
caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gauge and screw size for your drive
model. Place orders with a Yaskawa representative or the Yaskawa sales department.
The closed-loop crimp terminal sizes and values listed in
are Yaskawa recommendations. Refer to local codes for
proper selections.
Table D.9 Closed-Loop Crimp Terminal Sizes
Wire Gauge
Terminal
Screws
Crimp Terminal
Model Number
Tool
Insulation
Cap
Model No.
Code
<1>
Machine No.
Die Jaw
18 AWG
M3.5
R1.25-3.5
YA-4
AD-900
TP-003
100-066-217
16 AWG
M3.5
R1.25-3.5
YA-4
AD-900
TP-003
100-066-217
14 AWG
M3.5
R2-3.5
YA-4
AD-900
TP-003
100-066-218
M4
R2-4
YA-4
AD-900
TP-003
100-054-028
12 / 10 AWG
M4
R5.5-4
YA-4
AD-900
TP-005
100-054-029
M5
R5.5-5
YA-4
AD-900
TP-005
100-054-030
8 AWG
M4
8-4
YA-4
AD-901
TP-008
100-054-031
M5
R8-5
YA-4
AD-901
TP-008
100-054-032
M8
R8-8
YA-4
AD-901
TP-008
100-061-111
6 AWG
M4
14-4
YA-4
AD-902
TP-014
100-66-220
M5
R14-5
YA-4
AD-902
TP-014
100-054-034
M6
R14-6
YA-5
AD-952
TP-014
100-051-261
M8
R14-8
YA-5
AD-952
TP-014
100-054-035
4 AWG
M6
R22-6
YA-5
AD-953
TP-022
100-051-262
M8
R22-8
YA-5
AD-953
TP-022
100-051-263
3 AWG
M8
R38-8
YA-5
AD-954
TP-038
100-051-264
2 AWG
M8
R38-8
YA-5
AD-954
TP-038
100-051-264
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
Example: Models with 14 AWG for both input and output require one set for input terminals and one set for output terminals, so the user should
order two sets of [100-066-218].
Note:
Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is greater than 2% of motor
rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following formula to calculate the amount of voltage drop:
Line drop voltage (V) = 3 × wire resistance (Ω/km) × wire length (m) × current (A) × 10
-3
D.3 UL and CSA Standards
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
477
D
Standards Compliance