A.2 Single/Three-Phase 200 V Class Drives
Note:
Differences between Heavy Duty (HD) ratings and Normal Duty (ND) ratings for the drive include rated input and output current, overload
capacity, carrier frequency and current limit. Set parameter C6-01 to 0 for HD or 1 for ND (default).
Table A.2 Power Ratings
Item
Specification
Three-Phase Drive Model
2A0001
2A0002
2A0004
2A0006
2A0010
2A0012
2A0020
Single-Phase Drive Model
<1>
BA0001
BA0002
BA0003
BA0006
BA0010
BA0012
BA0018
Maximum Motor Size Allowed (HP)
<3>
ND Rating
0.13
0.25
0.5/
0.75
1.0/
1.5
2.0/
3.0
3.0
5.0
<2>
HD Rating
0.13
0.25
0.5
0.75/
1.0
1.5/
2.0
3.0
5.0
Input
Input Current
(A)
<4>
Three-
phase
ND Rating
1.1
1.9
3.9
7.3
10.8
13.9
24.0
<2>
HD Rating
0.7
1.5
2.9
5.8
7.5
11.0
18.9
Single-
phase
ND Rating
2.0
3.6
7.3
13.8
20.2
24.0
–
HD Rating
1.4
2.8
5.5
11.0
14.1
20.6
35.0
Output
Rated Output Capacity
(kVA)
<5>
ND Rating
0.5
0.7
1.3
2.3
3.7
4.6
7.5
<2>
HD Rating
0.3
0.6
1.1
1.9
3.0
4.2
6.7
Output Current (A)
ND Rating
<6>
1.2
1.9
3.5 (3.3)
6.0
9.6
12.0
19.6
<2>
HD Rating
0.8
<7>
1.6
<7>
3.0
<7>
5.0
<7>
8.0
<8>
11.0
<8>
17.5
<8>
Overload Tolerance
ND Rating: 120% of rated output current for 1 minute
HD Rating: 150% of rated output current for 1 minute
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User-adjustable 2 to 15 kHz
Max Output Voltage (V)
Three-phase power: 200 to 240 V
Single-phase power: 200 to 240 V
(both proportional to input voltage)
Max Output Frequency (Hz)
400 Hz (user-adjustable)
Power
Supply
Rated Voltage
Rated Frequency
Three-phase power: 200 to 240 V 50/60 Hz
Single-phase power: 200 to 240 V 50/60 Hz
DC power supply: 270 to 340 V
<9>
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Harmonic Corrective
Actions
DC Link Choke
Optional
<1> Drives with single-phase power supply input will output three-phase power and cannot run a single-phase motor.
<2> 2A0020 only. BA0018 is available with a Heavy Duty rating only.
<3> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor rated current.
<4> Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and power supply impedance.
<5> Rated motor capacity is calculated with a rated output voltage of 230 V.
<6> Carrier frequency is set to 2 kHz (Swing PWM). Current derating is required in order to raise the carrier frequency.
<7> Carrier frequency is set to 10 kHz. Current derating is required in order to raise the carrier frequency.
<8> Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency.
<9> DC is not available for UL standards.
A.2 Single/Three-Phase 200 V Class Drives
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
343
A
Specifications