No.
Parameter Name
Setting Range
Default
E4-15
Motor 2 Torque Compensation Gain
0.0 to 2.50
1.00
u
E5: PM Motor Settings
These parameters set the motor data of a PM motor used in OLV for PM (A1-02 = 5).
When Yaskawa motors are used, entering the motor code written on the motor nameplate will set up the E5-
oo
parameters.
For all other PM motors, the data must be entered manually.
n
E5-01: PM Motor Code Selection
Set the motor code for the PM motor being used. Depending on the motor code entered, the drive automatically sets several
parameters to appropriate values.
Refer to Parameters that Change with the Motor Code Selection on page 417
for details
on the supported motor codes and their parameter settings.
No.
Parameter Name
Setting Range
Default
E5-01
PM Motor Code Selection
0000 to FFFF
Depending on
o2-04
Note:
1.
This parameter is not reset when the drive is initialized using parameter A1-03.
2.
The default setting is for a Yaskawa SMRA Series SPM Motor with a speed rating of 1800 r/min.
3.
Changing the motor code setting resets all E5-
oo
settings to their default values.
4.
Set to “FFFF” when using a non-Yaskawa PM motor or one that is not supported by the motor code settings.
explains the motor code setting.
0 0 0 0
0: 1800 r/min Series
1: 3600 r/min Series
2: 1750 r/min Series
3: 1450 r/min Series
4: 1150 r/min Series
F: Special Motor
Motor Voltage Class
and Capacity
0: Pico Motor
(SMRA Series)
1: Derated Torque for IPM
Motors
(SSR 1 Series)
Figure 5.44 PM Motor Code
n
E5-02: Motor Rated Power (PM OLV)
Sets the rated power of the motor.
No.
Parameter Name
Setting Range
Default
E5-02
Motor Rated Power
0.10 to 18.50 kW
Depending on
E5-01
Note:
This parameter is not reset when the drive is initialized using A1-03.
n
E5-03: Motor Rated Current (PM OLV)
Sets the motor rated current in amps.
No.
Parameter Name
Setting Range
Default
E5-03
Motor Rated Current
10 to 200% of drive rated
current
Depending on
E5-01
Note:
1.
Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units.
2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units.
2.
This parameter is not reset when the drive is initialized using A1-03.
n
E5-04: Number of Motor Poles (PM OLV)
Sets the number of motor poles.
No.
Parameter Name
Setting Range
Default
E5-04
Number of Motor Poles
2 to 48
Depending on
E5-01
Note:
This parameter is not reset when the drive is initialized using A1-03.
5.5 E: Motor Parameters
178
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual