5.1 A: Initialization
The initialization group contains parameters associated with initial setup of the drive. Parameters involving the display
language, access levels, initialization, and password are located in this group.
u
A1: Initialization
n
A1-00: Language Selection
Selects the display language for the digital operator.
Note:
This parameter is not reset when the drive is initialized using parameter A1-03.
No.
Parameter Name
Setting Range
Default
A1-00
Language Selection
0 to 7
0
Setting 0: English
Setting 1: Japanese
Setting 2: German
Setting 3: French
Setting 4: Italian
Setting 5: Spanish
Setting 6: Portuguese
Setting 7: Chinese
n
A1-01: Access Level Selection
Allows or restricts access to drive parameters.
No.
Parameter Name
Setting Range
Default
A1-01
Access Level Selection
0 to 2
2
Setting 0: Operation Only
Access is restricted to parameters A1-01, A1-04, A1-06, and all U monitor parameters.
Setting 1: User Parameters
Access to only a specific list of parameters set to A2-01 through A2-32. These User Parameters can be accessed using the
Setup mode of the digital operator.
Setting 2: Advanced Access Level (A) and Setup Access Level (S)
All parameters can be viewed and edited.
Notes on Parameter Access
• If the drive parameters are password protected by A1-04 and A1-05, parameters A1-00 through A1-03, A1-06, and all A2
parameters cannot be modified.
• If a digital input programmed for Program Lockout (H1-
oo
= 1B) is enabled, parameter values cannot be modified, even
though the A1-01 is set to 1 or 2.
• If parameters are changed via serial communication the parameters cannot be changed from the digital operator until an
Enter command is received from the serial communication.
n
A1-02: Control Method Selection
Selects the Control Method of the drive.
Note:
1.
Be sure to perform Auto-Tuning when using one of the vector control modes.
2.
Reinitializing the drive does not reset A1-02 to the factory default value.
No.
Parameter Name
Setting Range
Default
A1-02
Control Method Selection
0, 2, 5
0
Setting 0: V/f Control
• For general-purpose and multiple motor applications.
5.1 A: Initialization
116
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual